LoRaWAN-Based Smart Energy Monitoring System For University Lecture Halls
IOSR Journal of Electrical and Electronics Engineering · 2026-02 · 21 (2) · 19-26
DOI: 10.9790/0853-2102011926 ↗Kurz gefasst
Fachartikel in der Zeitschrift IOSR Journal of Electrical and Electronics Engineering, 2026-02. Verfasst von Van-Tu Vu Van-Tu Vu und 2 weiteren Autor:innen.
Abstract (Originalsprache)
Background
Amid rising electricity consumption in Vietnamese universities, lecture halls suffer from significant energy waste due to lighting, air conditioning, and laboratory equipment being left on unnecessarily outside scheduled hours. This issue contradicts Sustainable Development Goal 7 (Affordable and Clean Energy) and Vietnam’s National Power Development Plan VIII. A reliable, long-range, low-power real-time energy monitoring system is essential for dense concrete educational buildings. Materials and Methods: This study develops a LoRaWAN-based smart energy monitoring system using a threelayer architecture. End-devices consist of Heltec WiFi LoRa 32 V4 nodes (ESP32-S3 + SX1262) integrated with PZEM-004T sensors for accurate AC power measurement and relay modules for automatic load control. The gateway employs a RAK5146 concentrator (SX1303) mounted on Raspberry Pi 5 with an 8 dBi outdoor antenna. Data transmission follows LoRaWAN AS923-2 protocol to the ThingsBoard or Easy LoRaWAN cloud platform. Simple AI models (Linear Regression and Multi-Layer Perceptron Neural Network) are implemented in the cloud for real-time waste detection, consumption prediction, anomaly alerts, and automated relay actuation. Node firmware is developed using Arduino/ESP-IDF, while cloud-side processing utilizes Python with scikit-learn and TensorFlow Lite.
Results
A three-month pilot deployment was conducted in Building C6 – a six-floor lecture facility with 40 classrooms and laboratories at Haiphong University – using five monitoring nodes and one central gateway. Daily energy consumption decreased from 130 kWh to 100 kWh, achieving 22.5% energy savings through automated detection and control of wasteful loads. The system demonstrated robust communication performance with a Packet Delivery Ratio (PDR) of 98.7% and RSSI values ranging from –85 dBm to –110 dBm in dense concrete structures. The AI models achieved prediction errors below 8% and 85% accuracy in automated waste detection.
Conclusion
The proposed LoRaWAN-based smart energy monitoring system proves highly effective, low-cost, and technically feasible for university lecture halls in Vietnam. It delivers significant energy savings while providing an excellent practical training platform for Electrical and Electronics Engineering students. The solution strongly contributes to digital transformation and sustainable energy practices in higher education institutions.
Zitieren
APA
Vu, V. V. V., Bui, V., & Nguyen, T. (2026). LoRaWAN-Based Smart Energy Monitoring System For University Lecture Halls. IOSR Journal of Electrical and Electronics Engineering, 21(2), 19-26. https://doi.org/10.9790/0853-2102011926
Vancouver
Vu VVV, Bui V, Nguyen T. LoRaWAN-Based Smart Energy Monitoring System For University Lecture Halls. IOSR Journal of Electrical and Electronics Engineering. 2026;21(2):19-26. doi:10.9790/0853-2102011926
BibTeX
@article{Vu2026,
author = {Vu, Van-Tu Vu Van-Tu and Bui, Van-Diep and Nguyen, Thi-Thu-Hien},
title = {LoRaWAN-Based Smart Energy Monitoring System For University Lecture Halls},
journal = {IOSR Journal of Electrical and Electronics Engineering},
year = {2026},
volume = {21},
number = {2},
pages = {19--26},
doi = {10.9790/0853-2102011926}
}