EUVIMEDEUVIMED entdecken
Open Access · CC BY-NC 3.0

Simulation-based Cooling Load Comparison for Small Server Rooms

Won Hyeong Lee, Do Yeong Jung, Seung Heon Lee, Jun Geon Park, Dong Kun Song, Hyeon Do Han, Da Hye Geum, Gyeong Won Min, Gu Young Cho

Journal of the Korean Society for Precision Engineering · 01.07.2026 · 43 (7) · 779-786

DOI: 10.7736/jkspe.025.00040 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Journal of the Korean Society for Precision Engineering, erschienen am 01.07.2026. Verfasst von Won Hyeong Lee und 8 weiteren Autor:innen. Die Arbeit nennt 10 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 3.0). Gefördert von: Ministry of Science and ICT, National Research Foundation of Korea, Ministry of Trade, Industry and Energy.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

With the rapid growth of AI and Big Data, reducing energy consumption in data centers has become a significant challenge. Small-scale server rooms, which often depend on standalone cooling units instead of specialized infrastructure, are especially vulnerable to airflow inefficiencies and localized hotspots. While traditional HVAC theory can estimate total cooling loads, it does not effectively predict the local thermal distributions that depend on equipment placement. This study employs Computational Fluid Dynamics (CFD) to address these limitations. It focuses on a server room containing five HPCs and three cooling units, comparing theoretical HVAC calculations with 3D thermal fluid analysis conducted using Ansys Fluent. The research evaluates the thermal performance of the existing layout (Model 1) and suggests an improved configuration (Model 2). The findings reveal that strategic equipment placement can eliminate hotspots and stabilize operations while reducing the necessary cooling capacity. This research provides a practical framework for enhancing energy efficiency in small-scale server environments.

Förderung

  • Ministry of Science and ICT
  • National Research Foundation of Korea
  • Ministry of Trade, Industry and Energy
  • Korea Institute for Advancement of Technology

Zitieren

APA

Lee, W. H., Jung, D. Y., Lee, S. H., Park, J. G., Song, D. K., Han, H. D., Geum, D. H., Min, G. W., & Cho, G. Y. (2026). Simulation-based Cooling Load Comparison for Small Server Rooms. Journal of the Korean Society for Precision Engineering, 43(7), 779-786. https://doi.org/10.7736/jkspe.025.00040

Vancouver

Lee WH, Jung DY, Lee SH, Park JG, Song DK, Han HD, et al. Simulation-based Cooling Load Comparison for Small Server Rooms. Journal of the Korean Society for Precision Engineering. 2026;43(7):779-786. doi:10.7736/jkspe.025.00040

BibTeX
@article{Lee2026,
  author = {Lee, Won Hyeong and Jung, Do Yeong and Lee, Seung Heon and Park, Jun Geon and Song, Dong Kun and Han, Hyeon Do and Geum, Da Hye and Min, Gyeong Won and Cho, Gu Young},
  title = {Simulation-based Cooling Load Comparison for Small Server Rooms},
  journal = {Journal of the Korean Society for Precision Engineering},
  year = {2026},
  volume = {43},
  number = {7},
  pages = {779--786},
  doi = {10.7736/jkspe.025.00040}
}