EUVIMEDEUVIMED entdecken
Open Access · CC BY-NC 4.0

Experimental Analysis of Pressure Differences in Vertical Spaces for Improving Smoke Control Systems Performance

Hyewon Kim, Hanbit Choi, Hyun Kang, Osang Kweon

International Journal of Fire Science and Engineering · 31.03.2026 · 40 (1) · 34-41

DOI: 10.7731/kifse.45e168b9 ↗

Kurz gefasst

Fachartikel in der Zeitschrift International Journal of Fire Science and Engineering, erschienen am 31.03.2026. Verfasst von Hyewon Kim und 3 weiteren Autor:innen. Die Arbeit nennt 11 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study aimed to establish a fundamental research basis for the design of smoke control systems considering fire scenarios. A six-story building scaled to 1/6 of full size was used as the experimental model, and the temperature distributions in the shaft and individual floor compartments were examined by varying the fire size (heat release rate). Pressure differences were calculated based on the measured temperature distributions. The results showed that, within the shaft space, temperatures were higher on the upper floors than on the lower floors, whereas the compartment temperatures on each floor tended to be higher on the lower floors. In addition, as the heat release rate increased, the pressure difference on the lower floors increased, while that on the upper floors decreased. These findings confirm that fire scenarios significantly influence the pressure difference distribution, highlighting the necessity of considering fire scenarios in the design of smoke control systems.

Zitieren

APA

Kim, H., Choi, H., Kang, H., & Kweon, O. (2026). Experimental Analysis of Pressure Differences in Vertical Spaces for Improving Smoke Control Systems Performance. International Journal of Fire Science and Engineering, 40(1), 34-41. https://doi.org/10.7731/kifse.45e168b9

Vancouver

Kim H, Choi H, Kang H, Kweon O. Experimental Analysis of Pressure Differences in Vertical Spaces for Improving Smoke Control Systems Performance. International Journal of Fire Science and Engineering. 2026;40(1):34-41. doi:10.7731/kifse.45e168b9

BibTeX
@article{Kim2026,
  author = {Kim, Hyewon and Choi, Hanbit and Kang, Hyun and Kweon, Osang},
  title = {Experimental Analysis of Pressure Differences in Vertical Spaces for Improving Smoke Control Systems Performance},
  journal = {International Journal of Fire Science and Engineering},
  year = {2026},
  volume = {40},
  number = {1},
  pages = {34--41},
  doi = {10.7731/kifse.45e168b9}
}