Measurement of Pyrolysis Properties for Fire Spread Simulation of Cables
Fire Science and Engineering · 31.12.2022 · 36 (6) · 38-47
DOI: 10.7731/kifse.25b7572e ↗Kurz gefasst
Fachartikel in der Zeitschrift Fire Science and Engineering, erschienen am 31.12.2022. Verfasst von Sun-Yeo Mun und 3 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 29 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0). Gefördert von: Ministry of Trade, Industry and Energy, Korea Energy Technology Evaluation and Planning.
Abstract (Originalsprache)
The analysis and review of the thermal decomposition properties required for the fire spread simulation of cables composed of multiple materials were performed. Thus, a typical two-step pyrolysis reaction was identified independent of cable type. It is expected that the Kissinger and flynn–wall–ozawa (FWO) methods, which are calculated using various heating rates, more accurately predict fire spread than the input method that uses the and values calculated using a single heating rate. Consequently, in the case of flame-retardant cables (CLASS 1E and TFR-8), the Kissinger method is more likely to overestimate the fire spread rate than the FWO method. In the case of polyvinyl chloride (PVC) cables (vinyl cabtire power cable, VCTF), the fire spread rate may be underestimated.
Förderung
- Ministry of Trade, Industry and Energy
- Korea Energy Technology Evaluation and Planning
Zitieren
APA
Mun, S., Cho, J., Lee, H., & Hwang, C. (2022). Measurement of Pyrolysis Properties for Fire Spread Simulation of Cables. Fire Science and Engineering, 36(6), 38-47. https://doi.org/10.7731/kifse.25b7572e
Vancouver
Mun S, Cho J, Lee H, Hwang C. Measurement of Pyrolysis Properties for Fire Spread Simulation of Cables. Fire Science and Engineering. 2022;36(6):38-47. doi:10.7731/kifse.25b7572e
BibTeX
@article{Mun2022,
author = {Mun, Sun-Yeo and Cho, Jae-Ho and Lee, Hong-In and Hwang, Cheol-Hong},
title = {Measurement of Pyrolysis Properties for Fire Spread Simulation of Cables},
journal = {Fire Science and Engineering},
year = {2022},
volume = {36},
number = {6},
pages = {38--47},
doi = {10.7731/kifse.25b7572e}
}