The effect of a hybrid PV-BESS system on voltage level, transient processes and power balance in a single-phase residential grid: a 2 × 2 factorial analysis under non-linear load conditions
Journal of Mathematical Models and Methods in Engineering · 16.11.2026 · 3 (1)
DOI: 10.66901/yfdnkc07 ↗Kurz gefasst
Fachartikel in der Zeitschrift Journal of Mathematical Models and Methods in Engineering, online erschienen am 16.11.2026. Verfasst von Mansurjon Abdujalilov und 1 weiteren Autor:innen.
Abstract (Originalsprache)
Rooftop PV systems, some with batteries, are spreading quickly in Uzbek households. We studied how such a system affects the supply voltage using a switching-level MATLAB/Simulink model of a hybrid PV-BESS system (3053 W PV array, 120 V / 100 Ah Li-ion battery, 400 V DC link) on a 220 V, 50 Hz single-phase grid. Irradiance (1 or 1000 W/m²) and load (5 kW linear, with or without a capacitor-filtered rectifier) formed a 2 × 2 design, and the PCC voltage was assessed per IEC 61000-4-30 against GOST 32144-2013 and GOST 13109-97. PV operation raised the PCC voltage by 1.48 percentage points on average, while the rectifier lowered it by 0.69 points. The effects were additive and matched the grid-impedance voltage drop within 0.02 V, which places the +5 % and +10 % levels at about 6.7 and 14 kW of export. In steady state the frequency deviation was below 10⁻⁶ Hz and the voltage fluctuation at most 0.0023 %, no dips or swells occurred, and MPPT efficiency was 99.13 %. The weak points were elsewhere. At start-up the DC-link voltage overshot to 455.9 V (14 %), and because the PI controller has no anti-windup, it settled in 0.27–0.29 s with PV instead of 0.055 s. The energy management system (EMS) computes the battery current from the nominal 120 V instead of the actual ≈128 V. As a result, the battery supplied 6.6 % more power than planned, the inverter output exceeded 5 kW and, with PV in operation, the bridge current came within 1.7–2.0 A of its 35 A limit.
Zitieren
APA
Abdujalilov, M., & Siddikov, I. (2026). The effect of a hybrid PV-BESS system on voltage level, transient processes and power balance in a single-phase residential grid: a 2 × 2 factorial analysis under non-linear load conditions. Journal of Mathematical Models and Methods in Engineering, 3(1). https://doi.org/10.66901/yfdnkc07
Vancouver
Abdujalilov M, Siddikov I. The effect of a hybrid PV-BESS system on voltage level, transient processes and power balance in a single-phase residential grid: a 2 × 2 factorial analysis under non-linear load conditions. Journal of Mathematical Models and Methods in Engineering. 2026;3(1). doi:10.66901/yfdnkc07
BibTeX
@article{Abdujalilov2026,
author = {Abdujalilov, Mansurjon and Siddikov, Ilxomjon},
title = {The effect of a hybrid PV-BESS system on voltage level, transient processes and power balance in a single-phase residential grid: a 2 × 2 factorial analysis under non-linear load conditions},
journal = {Journal of Mathematical Models and Methods in Engineering},
year = {2026},
volume = {3},
number = {1},
doi = {10.66901/yfdnkc07}
}
EUVIMED