Analysis of gas pressure decline SF6 in 70kV circuit breaker bay transformer 3 at Babakan substation
Journal of Emerging Innovations in Engineering · 2025
DOI: 10.65664/jeie.v1i02.8 ↗Kurz gefasst
Fachartikel in der Zeitschrift Journal of Emerging Innovations in Engineering, 2025. Verfasst von Arif Ramdhan Achmad und 2 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
This study analyzes the decrease in SF₆ gas pressure in the 70 kV circuit breaker Transformer Bay 3 at Babakan Substation, which affects the reliability of the power system. SF₆ gas is used as an insulating medium due to its high dielectric strength but is susceptible to micro-leakage, which degrades equipment performance. This research employs a qualitative approach with a case study strategy based on primary data obtained from field observations, interviews, and testing documentation before and after the replacement of the T-phase pole. Gas pressure monitoring was conducted using a FLIR Gas 306 camera and digital measuring instruments, with thematic analysis employed to identify causes and evaluate repair effectiveness. The results showed that a fine leak at the lower T-phase pole was the main cause of gas pressure reduction. After pole replacement, the rate of pressure drop decreased from 0.00459 MPa/day to 0.00016 MPa/day, indicating a 35.3% increase in insulation effectiveness and a 64.6% reduction in leakage rate. Operational feasibility tests met the SPLN 52-1:1983 standard, confirming that the circuit breaker is suitable for operation. I while applying condition-based maintenance (CBM) and infrared detection proved efficient in identifying SF₆ leakage and supporting predictive maintenance practices at substations.
Zitieren
APA
Achmad, A. R., Soleh, M., & Suprijadi, S. (2025). Analysis of gas pressure decline SF6 in 70kV circuit breaker bay transformer 3 at Babakan substation. Journal of Emerging Innovations in Engineering. https://doi.org/10.65664/jeie.v1i02.8
Vancouver
Achmad AR, Soleh M, Suprijadi S. Analysis of gas pressure decline SF6 in 70kV circuit breaker bay transformer 3 at Babakan substation. Journal of Emerging Innovations in Engineering. 2025. doi:10.65664/jeie.v1i02.8
BibTeX
@article{Achmad2025,
author = {Achmad, Arif Ramdhan and Soleh, Muhammad and Suprijadi, Sugeng},
title = {Analysis of gas pressure decline SF6 in 70kV circuit breaker bay transformer 3 at Babakan substation},
journal = {Journal of Emerging Innovations in Engineering},
year = {2025},
doi = {10.65664/jeie.v1i02.8}
}
EUVIMED