Abstract (Originalsprache)

Infrared thermography detects hot spots only at the time of inspection, whereas electrical system degradation evolves continuously through the 24/7 accumulation of operational stress. This study proposes a novel mechanism-informed predictive monitoring framework that integrates long-term three-phase current data with a physics-guided machine-learning inference model to identify early degradation signatures before infrared-detectable heating occurs. Results synthesized from multiple degradation indicators reveal that Phase B exhibits persistent structural dominance, with a mean occupancy of 56% (peaking at 71%), and accumulates 2.35 times the thermal debt of Phase A. This imbalance produces pronounced thermal memory, whereby 38% of thermal stress remains unrecovered after load reduction, resulting in the fastest insulation aging (aging rate = 0.0028; final Aging Index = 0.95). Notably, the proposed system degradation collapse index exceeds the critical degradation threshold (0.70) despite the absence of overload or fault conditions under conventional protection criteria. The proposed framework provides a continuous, low-cost, and practical solution for 24/7 predictive condition monitoring, enabling electrical hazards to be identified before hot spots and failures occur while overcoming the limitations of snapshot-based inspections.

Zitieren

APA

Rojchaya, S., & karisan, S. (2026). Detection of Chronic Load Imbalance and Hot-Spot Risk in Building Electrical Systems using Long-Term Three-Phase Current Analysis and Mechanism-Informed Artificial Intelligence. Recent Science and Technology, 18(3), e271202. https://doi.org/10.65411/rst.2026.271202

Vancouver

Rojchaya S, karisan S. Detection of Chronic Load Imbalance and Hot-Spot Risk in Building Electrical Systems using Long-Term Three-Phase Current Analysis and Mechanism-Informed Artificial Intelligence. Recent Science and Technology. 2026;18(3):e271202. doi:10.65411/rst.2026.271202

BibTeX
@article{Rojchaya2026,
  author = {Rojchaya, Sittisak and karisan, Santi},
  title = {Detection of Chronic Load Imbalance and Hot-Spot Risk in Building Electrical Systems using Long-Term Three-Phase Current Analysis and Mechanism-Informed Artificial Intelligence},
  journal = {Recent Science and Technology},
  year = {2026},
  volume = {18},
  number = {3},
  pages = {e271202},
  doi = {10.65411/rst.2026.271202}
}
Kostenlos starten →