Seismic retrofitting of civil hospital building, Ahmedabad – Case study
INDIAN CONCRETE JOURNAL · 2026 · 100 (10) · 41-57
DOI: 10.65302/icj.2026.100103 ↗Kurz gefasst
Fachartikel in der Zeitschrift INDIAN CONCRETE JOURNAL, 2026. Verfasst von SHAH UTSAV D und 2 weiteren Autor:innen.
Abstract (Originalsprache)
Seismic retrofitting is upgrading the seismic strength of damaged or existing buildings. Retrofitting reduces the vulnerability of damage to an existing structure during a nearfuture seismic activity. This paper presents a case study that involves a seismic retrofitting of the Civil Hospital (G-North Block) at Ahmedabad, originally built in the 1960s. The building is in seismic zone-III with Ground + 3 upper floors, having reinforced concrete ordinary moment resisting frame (OMRF) as its lateral load resisting system as was the best practice at the time of its construction. Mild steel reinforcement was used as reinforcement for all RC structural elements. After visual inspections and non-destructive testing (NDT), many deficiencies in the existing structure were found when checked with contemporary codal provisions. So, major seismic retrofitting of the structure was needed as per the present and future serviceability requirements. A 3D model analysis, considering in-situ material properties and structural details, was created in ETABS based on the existing structural layout of the building. Most of the columns were not safe for both the gravitational and lateral load. Concrete jacketing technique for beams and columns was used to improve the strength of the structure. The total base shear is now to be resisted by new shear walls in place of earlier OMRF. The fundamental time period of the retrofitted building was changed to 0.226 seconds as compared to 1.605 seconds for the existing structure. The base lateral load capacity of the retrofitted structure was enhanced by nearly two times that of the existing structure. An extremely nuanced retrofitting scheme with structural details was produced for the implementation at the site. This paper illustrates the detailed retrofitting technique, design methodology and its further in-situ execution procedure.
Zitieren
APA
D, S. U., V, P. P., & M, P. A. (2026). Seismic retrofitting of civil hospital building, Ahmedabad – Case study. INDIAN CONCRETE JOURNAL, 100(10), 41-57. https://doi.org/10.65302/icj.2026.100103
Vancouver
D SU, V PP, M PA. Seismic retrofitting of civil hospital building, Ahmedabad – Case study. INDIAN CONCRETE JOURNAL. 2026;100(10):41-57. doi:10.65302/icj.2026.100103
BibTeX
@article{D2026,
author = {D, SHAH UTSAV and V, PATEL PARESH and M, PATEL ASHISH},
title = {Seismic retrofitting of civil hospital building, Ahmedabad – Case study},
journal = {INDIAN CONCRETE JOURNAL},
year = {2026},
volume = {100},
number = {10},
pages = {41--57},
doi = {10.65302/icj.2026.100103}
}
EUVIMED