Assessment of Thermal Environment and Indoor Air Quality in University Buildings under Tropical Climate Conditions

Abayomi Temitope Layeni, Olanrewaju Adebola Lawal, Collins Neku Nwaokocha, Daniel Jesuyon Poheto, Elizabeth Ayobami Olumomi, Samson Oluwatobi Sogbaike

Faculty of Natural and Applied Sciences Journal of Scientific Innovations · 31.03.2026 · 7 (2) · 50-67

DOI: 10.63561/fnas-jsi.v7i2.1237 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Faculty of Natural and Applied Sciences Journal of Scientific Innovations, online erschienen am 31.03.2026. Verfasst von Abayomi Temitope Layeni und 5 weiteren Autor:innen.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study developed mathematical models for assessing the ventilation performance of a university lecture hall using thermal indoor air quality indicators, which focused on heat distribution and contaminant removal effectiveness. Ventilation effectiveness was modelled through the heat distribution effectiveness ratio (Et) and contaminant removal effectiveness ratio (Ec), developed from temperature and CO₂ concentration data collected at the supply, exhaust, and breathing zones. Data measurements of temperature, CO₂ concentration, and air velocity were collected across multiple zones during morning and afternoon lecture periods between February and April to capture variations in occupancy and outdoor conditions. Results revealed significant spatial and temporal variations in temperature (21.4–38.9 °C) and CO₂ levels (456–2673 ppm), with higher values typically occurring in the afternoon due to increased occupancy and reduced outdoor air supply. The evaluated Et values (0–1.2) indicated generally poor heat distribution and limited air mixing, while Ec values (0.1–0.7) suggested suboptimal contaminant removal, despite occasional improvements linked to increased outdoor air circulation. Occupancy-based ventilation analysis showed that outdoor air supply per person frequently fell below ASHRAE recommendations, particularly during peak afternoon periods. CONTAM airflow simulations corroborated the mathematical model developed from experimental results, indicating low infiltration rates during high occupancy. Overall, the findings demonstrate inadequate ventilation performance, leading to thermal discomfort and compromised indoor air quality, and underscore the need for improved ventilation strategies in densely occupied lecture halls.

Zitieren

APA

Layeni, A. T., Lawal, O. A., Nwaokocha, C. N., Poheto, D. J., Olumomi, E. A., & Sogbaike, S. O. (2026). Assessment of Thermal Environment and Indoor Air Quality in University Buildings under Tropical Climate Conditions. Faculty of Natural and Applied Sciences Journal of Scientific Innovations, 7(2), 50-67. https://doi.org/10.63561/fnas-jsi.v7i2.1237

Vancouver

Layeni AT, Lawal OA, Nwaokocha CN, Poheto DJ, Olumomi EA, Sogbaike SO. Assessment of Thermal Environment and Indoor Air Quality in University Buildings under Tropical Climate Conditions. Faculty of Natural and Applied Sciences Journal of Scientific Innovations. 2026;7(2):50-67. doi:10.63561/fnas-jsi.v7i2.1237

BibTeX
@article{Layeni2026,
  author = {Layeni, Abayomi Temitope and Lawal, Olanrewaju Adebola and Nwaokocha, Collins Neku and Poheto, Daniel Jesuyon and Olumomi, Elizabeth Ayobami and Sogbaike, Samson Oluwatobi},
  title = {Assessment of Thermal Environment and Indoor Air Quality in University Buildings under Tropical Climate Conditions},
  journal = {Faculty of Natural and Applied Sciences Journal of Scientific Innovations},
  year = {2026},
  volume = {7},
  number = {2},
  pages = {50--67},
  doi = {10.63561/fnas-jsi.v7i2.1237}
}
Kostenlos starten →