Fachartikel in der Zeitschrift International Journal of Electrical, Computer, and Biomedical Engineering, online erschienen am 30.12.2025. Verfasst von Elijah Chol Yom Majok und 1 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Dissolved gas analysis (DGA) is a very important and reliable technique for fault identification in transformers to prevent grid outage. However, DGA datasets are sometimes imbalanced and also affected by uncertainty due to the presence of varying levels of noise, and this reduces the prediction accuracy of classification models. In this paper, we proposed a hybrid approach that combines the Random Forest classifier with multiple resampling techniques such as Random Over-Sampling, SMOTE, ADASYN, Borderline-SMOTE (versions 1 and 2), SMOTE-ENN, and SMOTE-Tomek. These methods were evaluated to identify the best combinations under different levels of uncertainty. Experiments were done on a publicly accessible DGA dataset with the addition of Gaussian noise (0%-20%) that simulates practical uncertainty caused by data measurement errors. The results indicate that SMOTE obtained the highest average accuracy of 82.46% and 81.29% with training-testing splits of 70:30 and 80:20, respectively. In addition to SMOTE, random oversampling achieved the highest average accuracy of 83.19% using a 90:10 split. These accuracy values are averages across all noise levels tested. The results suggest that appropriate selection of a resampling method improves fault identification of a random forest classifier under Gaussian noise.

Zitieren

APA

Majok, E. C. Y., & Sudiarto, B. (2025). Power Transformer Fault Identification Based on Random Forest and Data Resampling Considering Data Uncertainty. International Journal of Electrical, Computer, and Biomedical Engineering, 3(4). https://doi.org/10.62146/ijecbe.v3i4.145

Vancouver

Majok ECY, Sudiarto B. Power Transformer Fault Identification Based on Random Forest and Data Resampling Considering Data Uncertainty. International Journal of Electrical, Computer, and Biomedical Engineering. 2025;3(4). doi:10.62146/ijecbe.v3i4.145

BibTeX
@article{Majok2025,
  author = {Majok, Elijah Chol Yom and Sudiarto, Budi},
  title = {Power Transformer Fault Identification Based on Random Forest and Data Resampling Considering Data Uncertainty},
  journal = {International Journal of Electrical, Computer, and Biomedical Engineering},
  year = {2025},
  volume = {3},
  number = {4},
  doi = {10.62146/ijecbe.v3i4.145}
}