EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Metrological traceability of touch voltage measurements using FSM concept in the high-voltage facility

Vojin Kostić, Željko Stojanović, Marko Marković

Tehnika · 2026 · 81 (3) · 269-279

DOI: 10.5937/tehnika2603269k ↗

Kurz gefasst

Fachartikel in der Zeitschrift Tehnika, 2026. Verfasst von Vojin Kostić und 2 weiteren Autor:innen. Die Arbeit nennt 16 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Ministry of Education, Science and Technological Development of the Republic of Serbia.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

In order to avoid interruption of service and costly downtime, touch voltage measurements are usually performed in an energized high-voltage substation. Due to conductive interference in the grounding system (usually several amperes, up to about 15 A), caused by power frequency, its harmonics and background noise, the energized high-voltage substation is an extremely challenging environment for the measurements of touch voltage. Under these conditions, ensuring confidence in the quality of the measurement results, by establishing metrological traceability, appears to be a complex research task. This paper presents the results of measuring touch voltage in the same high-voltage substation, but under significantly different environmental conditions and with a time interval of five years. On a practical example, on the basis of a statistically representative sample of eleven characteristic locations, it was clearly shown that the application of the FSM concept enables the establishment of metrological traceability of the touch voltages test results.

Förderung

  • Ministry of Education, Science and Technological Development of the Republic of Serbia

Zitieren

APA

Kostić, V., Stojanović, Ž., & Marković, M. (2026). Metrological traceability of touch voltage measurements using FSM concept in the high-voltage facility. Tehnika, 81(3), 269-279. https://doi.org/10.5937/tehnika2603269k

Vancouver

Kostić V, Stojanović Ž, Marković M. Metrological traceability of touch voltage measurements using FSM concept in the high-voltage facility. Tehnika. 2026;81(3):269-279. doi:10.5937/tehnika2603269k

BibTeX
@article{Kosti2026,
  author = {Kostić, Vojin and Stojanović, Željko and Marković, Marko},
  title = {Metrological traceability of touch voltage measurements using FSM concept in the high-voltage facility},
  journal = {Tehnika},
  year = {2026},
  volume = {81},
  number = {3},
  pages = {269--279},
  doi = {10.5937/tehnika2603269k}
}