Capacitor Bank Placement Enhancement Using Grey Wolf Algorithm for Reducing Harmonics in Low-Voltage Radial Distribution Networks
Equivalent: Jurnal Ilmiah Sosial Teknik · 16.07.2026 · 8 (3) · 896-908
DOI: 10.59261/jequi.v8i3.365 ↗Kurz gefasst
Fachartikel in der Zeitschrift Equivalent: Jurnal Ilmiah Sosial Teknik, online erschienen am 16.07.2026. Verfasst von Happy Aprillia und 3 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY-SA 4.0).
Abstract (Originalsprache)
Background
Low-voltage distribution systems are increasingly affected by harmonic distortion due to nonlinear loads, leading to power losses, reduced efficiency, and poor power quality. Capacitor banks are commonly used for reactive power compensation; however, improper placement may worsen harmonic conditions due to resonance effects.
Objective
This study aims to optimize capacitor bank placement in a low-voltage radial distribution system while improving power quality and minimizing harmonic distortion using the Grey Wolf Optimizer (GWO).
Method
A quantitative, simulation-based approach was applied using a 12-bus radial distribution model of an integrated laboratory system. Power flow analysis was conducted using the Backward/Forward Sweep (BFS) method, while optimization of capacitor placement and sizing was performed using the Grey Wolf Optimizer (GWO), considering multi-objective criteria including power loss, total harmonic distortion of current (THDI), total harmonic distortion of voltage (THDV), and power factor.
Result
The proposed GWO allocated a total of 1000 kVAr across selected buses, resulting in a 4.41% reduction in active power loss, a decrease in THDV from 6.181% to 1.517%, and an improvement in power factor to unity (1.0 pu). However, THDI remained at 18.71%, exceeding IEEE 519-2014 limits, indicating the need for additional harmonic filtering solutions.
Conclusion
The Grey Wolf Optimizer (GWO) is effective for optimizing capacitor placement and improving voltage-related power quality. However, additional harmonic mitigation techniques are required to comprehensively address current distortion.
Zitieren
APA
Aprillia, H., Septianto, O. R., Hasanah, B., & Suratno, S. (2026). Capacitor Bank Placement Enhancement Using Grey Wolf Algorithm for Reducing Harmonics in Low-Voltage Radial Distribution Networks. Equivalent: Jurnal Ilmiah Sosial Teknik, 8(3), 896-908. https://doi.org/10.59261/jequi.v8i3.365
Vancouver
Aprillia H, Septianto OR, Hasanah B, Suratno S. Capacitor Bank Placement Enhancement Using Grey Wolf Algorithm for Reducing Harmonics in Low-Voltage Radial Distribution Networks. Equivalent: Jurnal Ilmiah Sosial Teknik. 2026;8(3):896-908. doi:10.59261/jequi.v8i3.365
BibTeX
@article{Aprillia2026,
author = {Aprillia, Happy and Septianto, Oik Rizki and Hasanah, Barokatun and Suratno, Suratno},
title = {Capacitor Bank Placement Enhancement Using Grey Wolf Algorithm for Reducing Harmonics in Low-Voltage Radial Distribution Networks},
journal = {Equivalent: Jurnal Ilmiah Sosial Teknik},
year = {2026},
volume = {8},
number = {3},
pages = {896--908},
doi = {10.59261/jequi.v8i3.365}
}
EUVIMED