A full-scale watertight workflow numerical study for a triangular fin and tube heat exchanger
Turkish Journal of Mathematics · 01.09.2026 · 50 (5) · 970-988
DOI: 10.55730/1300-0098.3777 ↗Kurz gefasst
Fachartikel in der Zeitschrift Turkish Journal of Mathematics, online erschienen am 01.09.2026. Verfasst von HAMDİ SELÇUK ÇELİK und 2 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
In this study, the thermo-hydraulic characteristics of an air-cooled triangular finned tube heat exchanger were analyzed numerically. The full-scale heat exchanger was modeled using Ansys Fluent watertight workflow, considering water as the primer fluid to precisely investigate the effects of geometrical factors. The effects of fin height, fin width, and fin spacing of the triangular fins on the performance of the heat exchanger were examined using k-ω turbulence model. A basic finned-tube heat exchanger model, which was manufactured as a monolithic structure without tube-fin contact resistance by milling from aluminum 5083 material, was tested in an air tunnel to verify the numerical model in the Reynolds number range of 900-6000. The outcomes reveal that the triangular fin profile offers unique hydraulic advantages; unlike conventional designs, increasing the fin width or decreasing the fin pitch led to a reduction in the friction factor. This is attributed to the aerodynamic profile mitigating flow separation and the relative increase in surface area outweighing the rise in pressure drop. Based on an analysis of 66 different triangular fin geometries, novel empirical correlations were formulated to predict air-side performance. The resulting Nusselt number correlation captures 96% of the data within a ±4% error band, while the friction factor correlation accounts for 94% of the data within ±10%. Mean deviations for the proposed Nusselt number and f-factor correlations were calculated at 1.8% and 4.2%, confirming the high predictive reliability of both expressions.
Zitieren
APA
ÇELİK, H. S., DOĞAN, B., & ERBAY, L. B. (2026). A full-scale watertight workflow numerical study for a triangular fin and tube heat exchanger. Turkish Journal of Mathematics, 50(5), 970-988. https://doi.org/10.55730/1300-0098.3777
Vancouver
ÇELİK HS, DOĞAN B, ERBAY LB. A full-scale watertight workflow numerical study for a triangular fin and tube heat exchanger. Turkish Journal of Mathematics. 2026;50(5):970-988. doi:10.55730/1300-0098.3777
BibTeX
@article{ELK2026,
author = {ÇELİK, HAMDİ SELÇUK and DOĞAN, BAHADIR and ERBAY, LATİFE BERRİN},
title = {A full-scale watertight workflow numerical study for a triangular fin and tube heat exchanger},
journal = {Turkish Journal of Mathematics},
year = {2026},
volume = {50},
number = {5},
pages = {970--988},
doi = {10.55730/1300-0098.3777}
}
EUVIMED