EXPERIMENTAL INVESTIGATION OF THE EFFECT OF DIFFERENT RECTIFIER TOPOLOGIES ON OUTPUT VOLTAGE AND TOTAL HARMONIC DISTORTION IN SYNCHRONOUS ALTERNATOR EXCITATION

Mehmet Ali Özçelik, Ahmet Aycan, Mesut Özdinç

International Journal of Energy and Smart Grid · 22.11.2026 · 11

DOI: 10.55088/ijesg.2059401 ↗

Kurz gefasst

Fachartikel in der Zeitschrift International Journal of Energy and Smart Grid, online erschienen am 22.11.2026. Verfasst von Mehmet Ali Özçelik und 2 weiteren Autor:innen. Die Arbeit nennt 11 Literaturangaben.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

In this study, the effects of supplying the field (excitation) winding of a synchronous alternator through single-phase half-wave, single-phase full-wave, three-phase half-wave (3-pulse), and three-phase full-wave (6-pulse) rectifier circuits on the no-load stator output voltage and total harmonic distortion were experimentally investigated. The test machine was a synchronous alternator with the following nameplate specifications: 220/380 V (Δ/Y), 2.9/1.7 A (Δ/Y), 1.1 kVA, power factor cos φ = 0.8, rated speed 3000 rpm, 2p = 2 poles, 50 Hz. The measured field winding resistance was R = 197.2 Ω and inductance L = 1743.3 mH, yielding a time constant τ = L/R ≈ 8.84 ms. Measurements were performed on the stator phase-to-neutral voltages using a True RMS power analyser with an accuracy class of ±1% ±1 digit and a harmonic measurement range up to the 40th order. Under excitation currents ranging from 100 mA to 300 mA, the stator phase voltage total harmonic distortion remained nearly constant at approximately 7.1%–8.4% across all rectifier topologies. This finding indicates that the high inductance of the field winding attenuates the supply voltage ripple, acting as a natural low-pass filter and producing a smooth direct current in the field circuit. The results suggest that, under no-load conditions and within the excitation current range studied, the dominant source of stator voltage harmonics is likely the internal design parameters of the alternator—such as stator–rotor geometry, slot pitch, and air-gap flux distribution—rather than the excitation supply topology. These findings are specific to the machine under investigation and the no-load operating conditions employed.

Zitieren

APA

Özçelik, M. A., Aycan, A., & Özdinç, M. (2026). EXPERIMENTAL INVESTIGATION OF THE EFFECT OF DIFFERENT RECTIFIER TOPOLOGIES ON OUTPUT VOLTAGE AND TOTAL HARMONIC DISTORTION IN SYNCHRONOUS ALTERNATOR EXCITATION. International Journal of Energy and Smart Grid, 11. https://doi.org/10.55088/ijesg.2059401

Vancouver

Özçelik MA, Aycan A, Özdinç M. EXPERIMENTAL INVESTIGATION OF THE EFFECT OF DIFFERENT RECTIFIER TOPOLOGIES ON OUTPUT VOLTAGE AND TOTAL HARMONIC DISTORTION IN SYNCHRONOUS ALTERNATOR EXCITATION. International Journal of Energy and Smart Grid. 2026;11. doi:10.55088/ijesg.2059401

BibTeX
@article{zelik2026,
  author = {Özçelik, Mehmet Ali and Aycan, Ahmet and Özdinç, Mesut},
  title = {EXPERIMENTAL INVESTIGATION OF THE EFFECT OF DIFFERENT RECTIFIER TOPOLOGIES ON OUTPUT VOLTAGE AND TOTAL HARMONIC DISTORTION IN SYNCHRONOUS ALTERNATOR EXCITATION},
  journal = {International Journal of Energy and Smart Grid},
  year = {2026},
  volume = {11},
  doi = {10.55088/ijesg.2059401}
}
Kostenlos starten →