Graded Diagnosis of 110 kV Porcelain Insulator Degradation based on Spatial Electric Field Distribution
International Journal of Energy · 30.10.2026 · 10 (3) · 35-39
DOI: 10.54097/29dpjk54 ↗Kurz gefasst
Fachartikel in der Zeitschrift International Journal of Energy, online erschienen am 30.10.2026. Verfasst von Jiong Liu und 4 weiteren Autor:innen. Die Arbeit nennt 12 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0).
Abstract (Originalsprache)
A graded diagnosis method for 110 kV porcelain insulator degradation is proposed based on spatial electric-field distribution. The study is limited to a seven-disc 110 kV porcelain suspension insulator string so that modeling, feature extraction, and validation remain focused on one practical operating scenario. First, a finite-element baseline model is built for the healthy 110 kV porcelain insulator string to obtain the axial electric-field distribution pattern. Second, continuous RMS samples acquired by an unmanned-aerial-vehicle-mounted all-fiber electric-field sensor are converted into electric-field intensity, interpolated, divided into seven adaptive segments, and represented by trimmed-mean disc-level features. Finally, a dual-index decision rule combining a dynamic-rate ratio and a standard-deviation ratio is developed, followed by a four-level disc degradation grading model. Laboratory experiments on 110 kV seven-disc strings show that the method can locate degraded discs and provide severity grades. In the tested cases, the recall is higher than 94.5%, the false alarm rate is below 5.5%, and a single analysis takes less than 15 s.
Zitieren
APA
Liu, J., Liang, M., Tang, H., Wang, Y., & Yang, L. (2026). Graded Diagnosis of 110 kV Porcelain Insulator Degradation based on Spatial Electric Field Distribution. International Journal of Energy, 10(3), 35-39. https://doi.org/10.54097/29dpjk54
Vancouver
Liu J, Liang M, Tang H, Wang Y, Yang L. Graded Diagnosis of 110 kV Porcelain Insulator Degradation based on Spatial Electric Field Distribution. International Journal of Energy. 2026;10(3):35-39. doi:10.54097/29dpjk54
BibTeX
@article{Liu2026,
author = {Liu, Jiong and Liang, Ming and Tang, Huan and Wang, Yongsheng and Yang, Le},
title = {Graded Diagnosis of 110 kV Porcelain Insulator Degradation based on Spatial Electric Field Distribution},
journal = {International Journal of Energy},
year = {2026},
volume = {10},
number = {3},
pages = {35--39},
doi = {10.54097/29dpjk54}
}