Numerical Simulation of Pressure Pulsation in a Two-stage Double-suction Centrifugal Pump for Ophthalmic Medical Centers
Journal of Applied Fluid Mechanics · 01.09.2026 · 19 (9)
DOI: 10.47176/jafm.19.9.4394 ↗Kurz gefasst
Fachartikel in der Zeitschrift Journal of Applied Fluid Mechanics, online erschienen am 01.09.2026. Verfasst von Y. Gong und 6 weiteren Autor:innen.
Abstract (Originalsprache)
In ophthalmic medical centers (OMCs), a major challenge with vibration control is that while the preference for sophisticated diagnostic equipment is very low vibration, centralized cooling systems demand high-capacity pumping power. To reconcile these conflicting needs, in this study, we targeted the hydraulic source of pipeline vibration—the two-stage double-suction centrifugal pump (TDCP). We performed a full-field unsteady simulation based on the Scale Adaptive Simulation (SAS) model for mapping pressure pulsation evolution. Results show a typical double peak type of distribution at the tongues of the transition channel and volute. A critical multi-stage interaction effect is identified: partial load operation (0.6Qn) triggers a massive recirculation vortex in the transition channel. This structure generates a high-amplitude, low-frequency (approx. 25 Hz) signal distinct from the blade passing frequency (fBPF), creating a resonance risk for long-distance piping. Conversely, pulsations in the second-stage volute are dominated by rotor–stator interaction (RSI) and scale monotonically with flow rate. We conclude that restricting TDCP operation to near-design conditions (1.0Qn) is the most effective strategy for dampening excitation, offering a theoretical basis for low-vibration hospital infrastructure.
Zitieren
APA
Gong, Y., Cao, X., Wang, Y., Zheng, Y., An, D., Ma, J., & Liu, Y. (2026). Numerical Simulation of Pressure Pulsation in a Two-stage Double-suction Centrifugal Pump for Ophthalmic Medical Centers. Journal of Applied Fluid Mechanics, 19(9). https://doi.org/10.47176/jafm.19.9.4394
Vancouver
Gong Y, Cao X, Wang Y, Zheng Y, An D, Ma J, et al. Numerical Simulation of Pressure Pulsation in a Two-stage Double-suction Centrifugal Pump for Ophthalmic Medical Centers. Journal of Applied Fluid Mechanics. 2026;19(9). doi:10.47176/jafm.19.9.4394
BibTeX
@article{Gong2026,
author = {Gong, Y. and Cao, X. and Wang, Y. and Zheng, Y. and An, D. and Ma, J. and Liu, Y.},
title = {Numerical Simulation of Pressure Pulsation in a Two-stage Double-suction Centrifugal Pump for Ophthalmic Medical Centers},
journal = {Journal of Applied Fluid Mechanics},
year = {2026},
volume = {19},
number = {9},
doi = {10.47176/jafm.19.9.4394}
}