EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Experimental Investigation of Operating Room Air Distribution in a Full-Scale Laboratory Chamber Using Particle Image Velocimetry and Flow Visualization

James McNeill, Jean Hertzberg, Zhiqiang(John) Zhai

Journal of Flow Control, Measurement & Visualization · 2013

DOI: 10.4236/jfcmv.2013.11005 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Journal of Flow Control, Measurement & Visualization, 2013. Verfasst von James McNeill und 2 weiteren Autor:innen. Die Arbeit wurde bisher 11-mal zitiert (Crossref) und nennt 22 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Room air distribution in hospital operating rooms (OR) is critical to the effective functioning of surgical procedures, but the air distribution patterns are governed by complex physics that are currently not well understood. Both qualitative and quantitative flow visualization techniques were used to evaluate the room air distribution in a full-scale chamber designed to simulate a hospital operating room. A laser sheet illumination technique was used to identify key features of the room air distribution, and particle image velocimetry (PIV) was used to measure the velocity field in a plane crossing the surgical site. Hospital operating rooms require the use of ASHRAE Group E diffusers in an array above the surgical table, providing downward, unidirectional, non-aspirating air flow across the sterile region of the room. The supply air jet is characterized by complex physics, including annular shape, impingement, buoyancy, a large jet to room aspect ratio, and recirculation. The large diameter of the jet relative to the room size makes the overall room air distribution highly sensitive to the parameters of the supply air. The air distribution pattern in the room was found to have relatively low velocity and turbulence near the supply air diffuser, but increasing velocity and turbulence in the shear region at the edge of the supply air jet. Flow visualization and PIV methods both demonstrated an angle of the shear layer inwards towards the center of the jet. This flow feature reduces the overall coverage area for the sterile air flow and may pose a risk to the protection of the surgical patient.

Zitieren

APA

McNeill, J., Hertzberg, J., & Zhai, Z. (2013). Experimental Investigation of Operating Room Air Distribution in a Full-Scale Laboratory Chamber Using Particle Image Velocimetry and Flow Visualization. Journal of Flow Control, Measurement & Visualization. https://doi.org/10.4236/jfcmv.2013.11005

Vancouver

McNeill J, Hertzberg J, Zhai Z. Experimental Investigation of Operating Room Air Distribution in a Full-Scale Laboratory Chamber Using Particle Image Velocimetry and Flow Visualization. Journal of Flow Control, Measurement & Visualization. 2013. doi:10.4236/jfcmv.2013.11005

BibTeX
@article{McNeill2013,
  author = {McNeill, James and Hertzberg, Jean and Zhai, Zhiqiang(John)},
  title = {Experimental Investigation of Operating Room Air Distribution in a Full-Scale Laboratory Chamber Using Particle Image Velocimetry and Flow Visualization},
  journal = {Journal of Flow Control, Measurement & Visualization},
  year = {2013},
  doi = {10.4236/jfcmv.2013.11005}
}
Kostenlos starten →