Energy Analysis and Solar Photovoltaic System Sizing for a Sub-Wet Bulb Evaporative Cooling System in Tropical Climate
International Journal of Innovative Science and Research Technology · 10.04.2026 · 3793
DOI: 10.38124/ijisrt/26mar1323 ↗Kurz gefasst
Fachartikel in der Zeitschrift International Journal of Innovative Science and Research Technology, online erschienen am 10.04.2026. Verfasst von O. O. und 8 weiteren Autor:innen. Die Arbeit nennt 21 Literaturangaben.
Abstract (Originalsprache)
This study presents the design of a solar photovoltaic (PV) power system designed from the first principle to power a 1 kW Sub-Wet Bulb Evaporative Cooling (SWEC) system for building comfort applications in Owerri, Nigeria. A cooling load of a pilot office space was estimated following ASHRAE standards, yielding a design cooling load of 0.978 kW (approximately 0.3 tons of refrigeration) at 8-hour daily operation. This load informed the sizing of SWEC components at a heat exchanger area of 1.4 m² and a total electrical load of 303 W comprising fan, pump, and data logger/ control system. The solar photovoltaic (PV) power system sizing were carried out considering system losses, depth of discharge, 8-hour noontime sunlight of Owerri, Nigeria. The results show that a 400 W solar array with a battery bank of 303 Ah at 12 V, configured as two 150 Ah batteries in parallel effectively powered the system, at an energy yield of over 7% more than the power needed to power the cooling system. The result demonstrated the viability of solar-powered evaporative cooling system for sustainable building applications.
Zitieren
APA
O., O., Mong, C., O., Nwufo, N., G., Nwaji, C., A., Okoronkwo, & Anyanwu, E. E. (2026). Energy Analysis and Solar Photovoltaic System Sizing for a Sub-Wet Bulb Evaporative Cooling System in Tropical Climate. International Journal of Innovative Science and Research Technology, 3793. https://doi.org/10.38124/ijisrt/26mar1323
Vancouver
O. O, Mong, C. O, Nwufo, N. G, Nwaji, et al. Energy Analysis and Solar Photovoltaic System Sizing for a Sub-Wet Bulb Evaporative Cooling System in Tropical Climate. International Journal of Innovative Science and Research Technology. 2026:3793. doi:10.38124/ijisrt/26mar1323
BibTeX
@article{O2026,
author = {O., O. and Mong and C., O. and Nwufo and N., G. and Nwaji and C., A. and Okoronkwo and Anyanwu, E. E.},
title = {Energy Analysis and Solar Photovoltaic System Sizing for a Sub-Wet Bulb Evaporative Cooling System in Tropical Climate},
journal = {International Journal of Innovative Science and Research Technology},
year = {2026},
pages = {3793},
doi = {10.38124/ijisrt/26mar1323}
}