EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Experimental Investigation of a Miniature Refrigeration System Using R134a and a Low GWP Blend R515B

Juan Carlos Silva-Romero, José Luis Rodríguez-Muñoz, Francisco Noé Demesa-López, Donato Hernández-Fusilier, Vicente Pérez-García, Juan Manuel Belman-Flores

Thermo · 19.05.2026 · 6 (2) · 36

DOI: 10.3390/thermo6020036 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Thermo, online erschienen am 19.05.2026. Verfasst von Juan Carlos Silva-Romero und 5 weiteren Autor:innen. Die Arbeit nennt 35 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: University of Guanajuato CIIC.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Miniature vapor compression refrigeration systems are gaining increasing relevance in cutting-edge applications such as drone docking station cooling, electric vehicle battery thermal management, portable medical and diagnostic devices, compact beverage dispensers, field-mounted telecom cabinet cooling, as well as the already established fields of electronics and personal cooling. These systems offer a promising pathway to localized and mobile cooling solutions. When coupled with the implementation of alternative low-GWP refrigerants that match or even enhance system performance, the result is a more efficient, environmentally responsible, and potentially sustainable refrigeration technology. Therefore, this study experimentally evaluates the performance of R515B as a low-GWP drop-in replacement for R134a in a miniature vapor compression refrigeration system. Key parameters were analyzed to determine the most suitable operating conditions, resulting in a capillary length of 1.25 m, refrigerant charge of 110 g, compressor speed of 4500 rpm, and high condenser fan speed, under which R515B achieved a COP of 5.16 and a cooling capacity of 252.20 W, representing improvements of 38% and 6.5%, respectively, compared to R134a. These results confirm the viability of R515B as an efficient, environmentally friendly alternative for miniature small-scale vapor compression systems.

Förderung

  • University of Guanajuato CIIC

Zitieren

APA

Silva-Romero, J. C., Rodríguez-Muñoz, J. L., Demesa-López, F. N., Hernández-Fusilier, D., Pérez-García, V., & Belman-Flores, J. M. (2026). Experimental Investigation of a Miniature Refrigeration System Using R134a and a Low GWP Blend R515B. Thermo, 6(2), 36. https://doi.org/10.3390/thermo6020036

Vancouver

Silva-Romero JC, Rodríguez-Muñoz JL, Demesa-López FN, Hernández-Fusilier D, Pérez-García V, Belman-Flores JM. Experimental Investigation of a Miniature Refrigeration System Using R134a and a Low GWP Blend R515B. Thermo. 2026;6(2):36. doi:10.3390/thermo6020036

BibTeX
@article{SilvaRomero2026,
  author = {Silva-Romero, Juan Carlos and Rodríguez-Muñoz, José Luis and Demesa-López, Francisco Noé and Hernández-Fusilier, Donato and Pérez-García, Vicente and Belman-Flores, Juan Manuel},
  title = {Experimental Investigation of a Miniature Refrigeration System Using R134a and a Low GWP Blend R515B},
  journal = {Thermo},
  year = {2026},
  volume = {6},
  number = {2},
  pages = {36},
  doi = {10.3390/thermo6020036}
}
Kostenlos starten →