Research on Flexible Response Strategy for Data Center Integrated Energy Systems Considering Dynamic Reliability Quantification
Sustainability · 06.11.2026 · 18 (21) · 11353
DOI: 10.3390/su182111353 ↗Kurz gefasst
Fachartikel in der Zeitschrift Sustainability, online erschienen am 06.11.2026. Verfasst von Liting Zhang und 6 weiteren Autor:innen. Die Arbeit nennt 31 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Young Scientists Fund of the National Natural Science Foundation of China.
Abstract (Originalsprache)
With the rapid development of artificial intelligence technologies and the increasing energy demand of data centers, energy systems need to be operated with increasing reliability and flexibility. To address operational risks caused by renewable energy fluctuations and random equipment failures, this study takes a distributed integrated energy system for a data center as the research object and proposes an optimal scheduling strategy that coordinates dynamic reliability and flexibility. First, a dynamic reliability assessment model is established using a sequential Monte Carlo simulation based on a two-state Markov model, and the system’s reliability is quantitatively evaluated using the loss of load probability (LOLP) and expected energy not supplied (EENS). Second, equipment-level and system-level flexibility margin models are developed, and a dynamic reliability baseline constraint is introduced to integrate reliability requirements and regulation capability into a unified optimal scheduling framework. Finally, a simulation case based on the characteristics of a data center in Lingang, Shanghai, is used to evaluate the proposed method under typical seasonal operating conditions. The results show that the proposed strategy can effectively improve energy supply reliability and operational flexibility. Under typical summer conditions, the EENS of the cooling system is reduced by 82.3% compared with the conventional strategy, while the total system operating cost is reduced by 10.93–15.16% under different seasonal conditions. The proposed framework provides an effective approach for the reliability–flexibility-coordinated operation of data center integrated energy systems.
Förderung
- Young Scientists Fund of the National Natural Science Foundation of China
Zitieren
APA
Zhang, L., Lai, S., Qian, F., Xu, X., Yang, Y., Song, L., & Li, Q. (2026). Research on Flexible Response Strategy for Data Center Integrated Energy Systems Considering Dynamic Reliability Quantification. Sustainability, 18(21), 11353. https://doi.org/10.3390/su182111353
Vancouver
Zhang L, Lai S, Qian F, Xu X, Yang Y, Song L, et al. Research on Flexible Response Strategy for Data Center Integrated Energy Systems Considering Dynamic Reliability Quantification. Sustainability. 2026;18(21):11353. doi:10.3390/su182111353
BibTeX
@article{Zhang2026,
author = {Zhang, Liting and Lai, Sipeng and Qian, Fanyue and Xu, Xi and Yang, Yongwen and Song, Lifei and Li, Qifen},
title = {Research on Flexible Response Strategy for Data Center Integrated Energy Systems Considering Dynamic Reliability Quantification},
journal = {Sustainability},