Neutral Harmonics in a Low-Voltage Campus Microgrid: Long-Term Power Quality Statistics and Standards-Based Mitigation to Reduce Losses and Improve Resilience

Jorge Muñoz-Pilco, Nelson Calvachi, Luis Tipán, Carlos Barrera-Singaña, David Muñoz, Juan D. Ramirez

Sustainability · 25.03.2026 · 18 (7) · 3201

DOI: 10.3390/su18073201 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sustainability, online erschienen am 25.03.2026. Verfasst von Jorge Muñoz-Pilco und 5 weiteren Autor:innen. Die Arbeit nennt 57 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Salesian Polytechnic University.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The energy transition and electrification are increasing the use of power electronics in low-voltage networks, increasing losses and reducing service availability when harmonic currents are concentrated in the neutral. This study statistically evaluates power quality in a campus-type microgrid with a high proportion of nonlinear loads. The novelty of the work lies in combining field measurements, percentile-based neutral-current severity analysis, and standards-based comparative mitigation assessment in a low-voltage 3P4W campus microgrid. A campaign was carried out using a Fluke 1775 analyzer, recording trends, frequency, and events. Approximately 1900 events were recorded, mainly waveform deviations, interruptions, and rapid voltage changes. Voltage distortion was moderate, with a 95th percentile between 3.6% and 3.8%, while the neutral conductor concentrated the highest severity: neutral-current THD exceeded 220% in the 95th percentile and reached maximums above 700%, with 16.78 A in the 95th percentile at the measurement point. Based on IEC 61000-2-2 and IEEE 519, four mitigation measures were evaluated in DIgSILENT PowerFactory 2024 to estimate and reduce losses and heating: load balancing, detuned compensation, passive filtering, and active filtering. Active mitigation reduced the neutral harmonic component by 80% and the combined strategy decreased the neutral current at the measuring point by 78% (16.78 A to 3.69 A), with an estimated reduction in resistive losses of close to 95%. These results suggest sustainability benefits by reducing energy wasted as heat, extending the useful life of the infrastructure and improving operational resilience.

Förderung

  • Salesian Polytechnic University

Zitieren

APA

Muñoz-Pilco, J., Calvachi, N., Tipán, L., Barrera-Singaña, C., Muñoz, D., & Ramirez, J. D. (2026). Neutral Harmonics in a Low-Voltage Campus Microgrid: Long-Term Power Quality Statistics and Standards-Based Mitigation to Reduce Losses and Improve Resilience. Sustainability, 18(7), 3201. https://doi.org/10.3390/su18073201

Vancouver

Muñoz-Pilco J, Calvachi N, Tipán L, Barrera-Singaña C, Muñoz D, Ramirez JD. Neutral Harmonics in a Low-Voltage Campus Microgrid: Long-Term Power Quality Statistics and Standards-Based Mitigation to Reduce Losses and Improve Resilience. Sustainability. 2026;18(7):3201. doi:10.3390/su18073201

BibTeX
@article{MuozPilco2026,
  author = {Muñoz-Pilco, Jorge and Calvachi, Nelson and Tipán, Luis and Barrera-Singaña, Carlos and Muñoz, David and Ramirez, Juan D.},
  title = {Neutral Harmonics in a Low-Voltage Campus Microgrid: Long-Term Power Quality Statistics and Standards-Based Mitigation to Reduce Losses and Improve Resilience},
  journal = {Sustainability},
  year = {2026},
  volume = {18},
  number = {7},
  pages = {3201},
  doi = {10.3390/su18073201}
}
Kostenlos starten →