EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Performance Analysis of Thermal Energy Storage Tanks and Chillers for Optimizing Cooling Efficiency in Smart Greenhouses in Hot and Arid Climates

Sul-Geon Choi, Doo-Yong Park, Doo-Sung Choi, Yong-Ho Jung

Sustainability · 19.12.2024 · 16 (24) · 11136

DOI: 10.3390/su162411136 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sustainability, online erschienen am 19.12.2024. Verfasst von Sul-Geon Choi und 3 weiteren Autor:innen. Die Arbeit wurde bisher 9-mal zitiert (Crossref) und nennt 26 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Ministry of Agriculture, Food and Rural Affairs (MAFRA), Ministry of Science and ICT (MSIT), Rural Development Administra-tion (RDA).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study analyzes the performance of thermal energy storage tanks and chillers in efficiently operating cooling systems for smart greenhouses in hot, arid climates such as the United Arab Emirates (UAE). The performance of chillers is heavily influenced by outdoor air temperatures, with the coefficient of performance (COP) of chillers decreasing and energy consumption increasing as daytime temperatures rise. This study found that when the outdoor air temperature reached 46.6 °C, the COP of the chiller dropped to 2.18, representing a 24.6% decrease compared to the COP of 2.89 at 35 °C. Conversely, at night, when the outdoor air temperature dropped to 28.3 °C, the chiller’s performance recovered, with the COP rising to 3.67. To address this, a strategy utilizing thermal energy storage tanks to store chilled water at night for use during the day was proposed, compensating for the decline in chiller performance. The results showed that when the thermal energy storage capacity was set at 40%, energy consumption decreased by up to 15%. However, while increasing the thermal energy storage capacity beyond 50% effectively reduced the peak load on the chiller, further increasing it beyond 60% led to a rise in chiller capacity and energy consumption. Therefore, this study concludes that setting the thermal energy storage capacity to no more than 50% is the most effective strategy to maximize chiller performance and reduce energy consumption. These findings provide crucial guidelines for the design and operation of cooling systems, offering valuable strategies to optimize the operation of smart greenhouses in hot climates.

Förderung

  • Ministry of Agriculture, Food and Rural Affairs (MAFRA)
  • Ministry of Science and ICT (MSIT)
  • Rural Development Administra-tion (RDA)

Zitieren

APA

Choi, S., Park, D., Choi, D., & Jung, Y. (2024). Performance Analysis of Thermal Energy Storage Tanks and Chillers for Optimizing Cooling Efficiency in Smart Greenhouses in Hot and Arid Climates. Sustainability, 16(24), 11136. https://doi.org/10.3390/su162411136

Vancouver

Choi S, Park D, Choi D, Jung Y. Performance Analysis of Thermal Energy Storage Tanks and Chillers for Optimizing Cooling Efficiency in Smart Greenhouses in Hot and Arid Climates. Sustainability. 2024;16(24):11136. doi:10.3390/su162411136

BibTeX
@article{Choi2024,
  author = {Choi, Sul-Geon and Park, Doo-Yong and Choi, Doo-Sung and Jung, Yong-Ho},
  title = {Performance Analysis of Thermal Energy Storage Tanks and Chillers for Optimizing Cooling Efficiency in Smart Greenhouses in Hot and Arid Climates},
  journal = {Sustainability},
  year = {2024},
  volume = {16},
  number = {24},
  pages = {11136},
  doi = {10.3390/su162411136}
}