EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Study on Effects of Operating Parameters on a Water-Cooled Loop Thermosyphon System under Partial Server Utilization

Sikai Zou, Chang Yue, Ting Xiao, Xingyi Ma, Yiwei Wang

Sustainability · 31.08.2023 · 15 (17) · 13100

DOI: 10.3390/su151713100 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sustainability, online erschienen am 31.08.2023. Verfasst von Sikai Zou und 4 weiteren Autor:innen. Die Arbeit wurde bisher 4-mal zitiert (Crossref) und nennt 48 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Natural Science Found of China, Jiangxi Provincial Natural Science Foundation, the Science and Technology Research Project of Education Department of Jiangxi Province.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

During the operation of a data center, servers are gradually installed in racks, causing most racks to work under a low heating load for a long time and affecting the cooling efficiency of the loop thermosyphon system (LTS). Thus, the effects of operating parameters on the thermal performance should be investigated. In this study, a water-cooled LTS was experimentally investigated under different airflow rates and heating loads. The results show that the additional liquid refrigerant reduced the heat transfer performance and aggravated a drop in cooling capacity when the airflow rate and heating load were decreased. To further reveal the effects of the operating parameters on the thermal performance and cooling efficiency, a steady-state distributed-parameter model was developed and validated based on the experimental data. The results show that the excessive cooling capacity was reduced by decreasing the airflow rate according to the upper limit of the server exhaust air temperature under partial server utilization. The excessive cooling capacity was reduced by 14.5–52.1% under 5–56.5% server utilization. To further reduce the excessive cooling capacity while ensuring thermal security, the water side operating parameters (including the supply chilled water temperature and water flow rate) were adjusted according to the upper limit of the rack’s average outlet air temperature, which reduced the excessive cooling capacity by more than 23.8% under partial server utilization.

Förderung

  • National Natural Science Found of China
  • Jiangxi Provincial Natural Science Foundation
  • the Science and Technology Research Project of Education Department of Jiangxi Province

Zitieren

APA

Zou, S., Yue, C., Xiao, T., Ma, X., & Wang, Y. (2023). Study on Effects of Operating Parameters on a Water-Cooled Loop Thermosyphon System under Partial Server Utilization. Sustainability, 15(17), 13100. https://doi.org/10.3390/su151713100

Vancouver

Zou S, Yue C, Xiao T, Ma X, Wang Y. Study on Effects of Operating Parameters on a Water-Cooled Loop Thermosyphon System under Partial Server Utilization. Sustainability. 2023;15(17):13100. doi:10.3390/su151713100

BibTeX
@article{Zou2023,
  author = {Zou, Sikai and Yue, Chang and Xiao, Ting and Ma, Xingyi and Wang, Yiwei},
  title = {Study on Effects of Operating Parameters on a Water-Cooled Loop Thermosyphon System under Partial Server Utilization},
  journal = {Sustainability},
  year = {2023},
  volume = {15},
  number = {17},
  pages = {13100},
  doi = {10.3390/su151713100}
}
Kostenlos starten →