Abstract (Originalsprache)

Grid-connected photovoltaic (PV) systems paired with battery storage are becoming a core element of low-carbon distribution networks. This paper develops a complete closed-form formulation together with an independent, simulation-based verification of a single-phase grid-connected PV-battery microgrid sized for high-irradiance residential conditions in Saudi Arabia, using measured solar-resource and tariff data for Riyadh. A 6.25 kW monocrystalline array feeds a 400 V DC link through a perturb-and-observe boost stage; a bidirectional converter couples a 13.5 kWh LiFePO4 battery; and an IEEE 1547 smart inverter interfaces a 230 V grid through an LCL filter. Governing equations for every subsystem are derived and evaluated numerically, and a Python re-implementation of the phasor power-flow model verifies the analysis over a 24 h cycle run to periodic steady state, reproducing the reference design values with a mean absolute error of 0.5%. Using measured monthly solar-resource and temperature data for Riyadh, a full twelve-month analysis gives an annual self-sufficiency of 51.8% and a PV self-consumption of 72.9% for the optimised energy-management scheme. A dedicated time-domain switching simulation with FFT analysis shows that the LCL filter limits grid-current total harmonic distortion to 0.8%, far below the L-filter value of 6.2% and below the 5% current-distortion reference of IEEE 519 (full compliance additionally requires the PCC short-circuit ratio). Twelve-month, battery-size and load-sensitivity studies confirm robustness, and a techno-economic assessment based on the Saudi Electricity Company residential tariff quantifies levelized cost, payback and battery degradation, showing that economic viability hinges on tariff reform.

Zitieren

APA

Hakami, A., Khan, M. A., Alshehri, A. M. A., Asiri, A. A. A., & Alhallafi, A. K. (2026). Theoretical Formulation and Simulation-Based Verification of a Grid-Connected Photovoltaic-Battery Microgrid with Smart-Inverter Support for High-Irradiance Residential Applications in Saudi Arabia. Solar, 6(4), 43. https://doi.org/10.3390/solar6040043

Vancouver

Hakami A, Khan MA, Alshehri AMA, Asiri AAA, Alhallafi AK. Theoretical Formulation and Simulation-Based Verification of a Grid-Connected Photovoltaic-Battery Microgrid with Smart-Inverter Support for High-Irradiance Residential Applications in Saudi Arabia. Solar. 2026;6(4):43. doi:10.3390/solar6040043

BibTeX
@article{Hakami2026,
  author = {Hakami, Abdullatif and Khan, Muhammed Anaz and Alshehri, Abdulkhaleq Mohammed Abdullah and Asiri, Ali Ahmad Ali and Alhallafi, Abdulrahman Khader},
  title = {Theoretical Formulation and Simulation-Based Verification of a Grid-Connected Photovoltaic-Battery Microgrid with Smart-Inverter Support for High-Irradiance Residential Applications in Saudi Arabia},
  journal = {Solar},
  year = {2026},
  volume = {6},
  number = {4},
  pages = {43},
  doi = {10.3390/solar6040043}
}
Kostenlos starten →