EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Measurement-Driven Koopman Dynamic Equivalencing with Modal Preservation for Small-Signal Stability Assessment of Power Systems

Weiran Jiao, Han Yan, Qian Sun, Mingyuan Wang, Jianfeng Zhao

Sensors · 22.11.2026 · 26 (23) · 7385

DOI: 10.3390/s26237385 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sensors, online erschienen am 22.11.2026. Verfasst von Weiran Jiao und 4 weiteren Autor:innen. Die Arbeit nennt 27 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Small-signal stability assessment of interconnected power systems requires a dynamic representation of neighboring areas whose detailed models may be unavailable. This study develops a measurement-driven Koopman dynamic equivalent using voltage-magnitude and phase-angle deviations at boundary buses as inputs and active- and reactive-power deviations on tie lines as outputs. A regularized regression in delay coordinates identifies the external-area input–output dynamics. Modal reduction prioritizes weakly damped modes with appreciable boundary-output salience and response energy. The reduced continuous-time realization is coupled to the detailed study-area model for eigenvalue analysis. In simulations of a 39-bus system, the dominant-mode frequency and damping-ratio errors were 0.11% and 1.41%, respectively, across cases with case-specific identification. A fixed equivalent evaluated on unseen load disturbances yielded errors of 0.141% and 1.865%, respectively. At a signal-to-noise ratio of 10 dB, the corresponding mean errors across 30 independent additive white Gaussian noise realizations were 0.978% and 7.351%. These results demonstrate the feasibility of boundary-measurement-based small-signal assessment in the simulated system and show that damping estimates are particularly sensitive to measurement noise.

Zitieren

APA

Jiao, W., Yan, H., Sun, Q., Wang, M., & Zhao, J. (2026). Measurement-Driven Koopman Dynamic Equivalencing with Modal Preservation for Small-Signal Stability Assessment of Power Systems. Sensors, 26(23), 7385. https://doi.org/10.3390/s26237385

Vancouver

Jiao W, Yan H, Sun Q, Wang M, Zhao J. Measurement-Driven Koopman Dynamic Equivalencing with Modal Preservation for Small-Signal Stability Assessment of Power Systems. Sensors. 2026;26(23):7385. doi:10.3390/s26237385

BibTeX
@article{Jiao2026,
  author = {Jiao, Weiran and Yan, Han and Sun, Qian and Wang, Mingyuan and Zhao, Jianfeng},
  title = {Measurement-Driven Koopman Dynamic Equivalencing with Modal Preservation for Small-Signal Stability Assessment of Power Systems},
  journal = {Sensors},
  year = {2026},
  volume = {26},
  number = {23},
  pages = {7385},
  doi = {10.3390/s26237385}
}
Kostenlos starten →