Comparative Analysis of Additional Measurement Error Introduced by Inductive Current Transformers, Rogowski Coils and Electronic Current Transducer for Harmonics of Distorted Current

Michal Kaczmarek iD, Michal Ozimek, Jerzy Cal iD

Sensors · 03.06.2026 · 26 (11) · 3546

DOI: 10.3390/s26113546 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sensors, online erschienen am 03.06.2026. Verfasst von Michal Kaczmarek und 2 weiteren Autor:innen. Beteiligte Einrichtung: Institute of Mechatronics and Information Systems, Lodz University of Technology, 90-537 Lodz, Poland. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This paper investigates the accuracy of conventional inductive current transformers (iCTs) and Rogowski coils (RCs) in measuring distorted currents, evaluating compliance with the WB0 (up to the 13th harmonic) and WB1 (up to the 60th harmonic) accuracy classes according to the IEC 61869-1 standard. A custom reference iCT, calibrated via the ampere-turns method to achieve a superior baseline accuracy (0.02%), served as the primary benchmark. A zero-flux electronic transducer was utilized strictly to verify this reference. Despite inherent core nonlinearity, tested conventional iCTs with reduced to minimum secondary burdens successfully met the class 0.5-WB1 requirements. In the case of tested Rogowski coils, the study reveals that their wideband performance depends on physical design of the particular type. High-sensitivity coils suffer from increased parasitic capacitance and self-inductance, causing significant additional phase shift at higher frequencies, whereas low-sensitivity, small-diameter coils offer superior linearity. Overall, the tested RCs generally ensured compliance with the 0.5-WB1 class across the evaluated frequency range, with certain units successfully achieving the more restrictive 0.2-WB1 class. Ultimately, conventional iCTs remain a highly reliable solution for metering purposes in low-voltage networks, while properly selected Rogowski coils provide a valuable alternative for power quality analysis and harmonic distortion measurements.

Schlagwörter

Stichwörter der Autor:innen

IEC 61869-1Rogowski coilWB0WB1conversion accuracyconversion errorcurrent distortioncurrent errorhigher harmonicinductive current transformeroptional wideband accuracy classesphase displacementphase shifttransformation accuracy

Autor:innen und Institutionen

  • Institute of Mechatronics and Information Systems, Lodz University of Technology, 90-537 Lodz, Poland.

ORCID-Profile: Michal Kaczmarek, Jerzy Cal

Zitieren

APA

Kaczmarek, M., Ozimek, M., & Cal, J. (2026). Comparative Analysis of Additional Measurement Error Introduced by Inductive Current Transformers, Rogowski Coils and Electronic Current Transducer for Harmonics of Distorted Current. Sensors, 26(11), 3546. https://doi.org/10.3390/s26113546

Vancouver

Kaczmarek M, Ozimek M, Cal J. Comparative Analysis of Additional Measurement Error Introduced by Inductive Current Transformers, Rogowski Coils and Electronic Current Transducer for Harmonics of Distorted Current. Sensors. 2026;26(11):3546. doi:10.3390/s26113546

BibTeX
@article{Kaczmarek2026,
  author = {Kaczmarek, Michal and Ozimek, Michal and Cal, Jerzy},
  title = {Comparative Analysis of Additional Measurement Error Introduced by Inductive Current Transformers, Rogowski Coils and Electronic Current Transducer for Harmonics of Distorted Current},
  journal = {Sensors},
  year = {2026},
  volume = {26},
  number = {11},
  pages = {3546},
  doi = {10.3390/s26113546}
}
Kostenlos starten →