A Novel Directional Element for AC Lines in Systems with Inverter-Based Resources

Kun Qian iD, Minghao Wen, Xiaoting Xue, Zichang Sun

Sensors · 09.05.2026 · 26 (10) · 2991

DOI: 10.3390/s26102991 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sensors, online erschienen am 09.05.2026. Verfasst von Kun Qian und 3 weiteren Autor:innen. Beteiligte Einrichtung: School of Electrical and Electronic Engineering, Huazhong University of Science and Technology, Wuhan 430074, China. Die Arbeit nennt 15 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Natural Science Foundation of China.

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The fault response of inverter-based resources (IBRs) is strongly influenced by their control strategies, which may significantly change the directional information available to line relays during non-ground faults. As a result, conventional directional elements designed according to the fault characteristics of conventional power systems may exhibit poor adaptability in IBR-connected systems. In particular, zero-sequence directional elements cannot be applied to non-ground faults, whereas negative-sequence-based schemes may be adversely affected by the fault-control behavior of IBRs. To address this problem, this paper proposes a directional element for non-ground faults on AC lines in systems with IBRs. First, the positive-sequence measured impedance at the relay locations is analyzed under typical fault conditions, and the dependence of available directional information on the phase characteristic of the IBR fault current is clarified. Then, a control–protection coordinated method is introduced to regulate the fault-current phase of the IBR during faults so that stable and consistent positive-sequence directional features can be established at both line terminals. On this basis, a unified directional criterion is formulated. Finally, PSCAD/EMTDC simulations are carried out to verify the proposed method, and dynamic model experiments are conducted to validate its engineering feasibility. The results show that the proposed element correctly identifies the fault direction under both three-phase and phase-to-phase fault conditions. Additional tests considering measurement noise and opposite-side grid-strength variation further demonstrate the robustness of the proposed criterion. Compared with conventional directional elements, the proposed method improves the adaptability of non-ground fault-direction identification in IBR-connected AC lines.

Schlagwörter

Stichwörter der Autor:innen

control–protection coordinationdirectional elementfault characteristicinverter-based resource (IBR)

Autor:innen und Institutionen

  • School of Electrical and Electronic Engineering, Huazhong University of Science and Technology, Wuhan 430074, China.
  • Nanjing SAC Power Grid Automation Co., Ltd., Nanjing 211153, China.
  • Nanjing Power Supply Branch, State Grid Jiangsu Electric Power Co., Ltd., Nanjing 211102, China.

ORCID-Profile: Kun Qian

Förderung

  • National Natural Science Foundation of China

Zitieren

APA

Qian, K., Wen, M., Xue, X., & Sun, Z. (2026). A Novel Directional Element for AC Lines in Systems with Inverter-Based Resources. Sensors, 26(10), 2991. https://doi.org/10.3390/s26102991

Vancouver

Qian K, Wen M, Xue X, Sun Z. A Novel Directional Element for AC Lines in Systems with Inverter-Based Resources. Sensors. 2026;26(10):2991. doi:10.3390/s26102991

BibTeX
@article{Qian2026,
  author = {Qian, Kun and Wen, Minghao and Xue, Xiaoting and Sun, Zichang},
  title = {A Novel Directional Element for AC Lines in Systems with Inverter-Based Resources},
  journal = {Sensors},
  year = {2026},
  volume = {26},
  number = {10},
  pages = {2991},
  doi = {10.3390/s26102991}
}
Kostenlos starten →