EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Online Monitoring of Transformer Winding Faults Based on Pulse Coupling Injection

Zetong Wang, Yuhan Zou, Junhao Ma, Zongnan Liu, Xinyu Peng, Tianran Zhang, Sizhe Xiang, Chenguo Yao, Shoulong Dong iD

Sensors · 06.05.2026 · 26 (9) · 2914

DOI: 10.3390/s26092914 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sensors, online erschienen am 06.05.2026. Verfasst von Zetong Wang und 8 weiteren Autor:innen. Beteiligte Einrichtung: State Key Laboratory of Power Transmission Equipment Technology, Chongqing University, Chongqing 400044, China. Die Arbeit nennt 23 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Aiming at the problems with traditional transformer winding deformation detection, requiring power outages, low signal-to-noise ratios for online monitoring, and insufficient feature extraction, this paper proposes a live monitoring and intelligent diagnosis method based on pulse-coupled injection. At the hardware level, a semi-ring capacitive coupling sensor is developed and designed, which realizes non-contact injection of high-frequency pulse signals and high-SNR extraction without a power outage. The reliability of the system under complex working conditions is verified by field experiments on multiple actual 110 kV transformers. At the algorithm level, an innovative MSCNN–Transformer–PGA deep composite model fused with prior electromagnetic physical knowledge is constructed and combined with the transformer equivalent circuit model. The model uses a multi-scale convolution to extract local details of frequency response signals, adopts Transformer to establish the global sequence dependence, and introduces a Physics-Guided Attention mechanism (PGA) to adaptively focus on the key fault physical frequency bands. The experimental results show that the proposed method effectively overcomes electromagnetic noise interference, and the fault classification accuracy of single-modal pulse frequency response data reaches 97.6%, providing a high-precision online monitoring solution for the safe operation and maintenance of transformers.

Schlagwörter

Stichwörter der Autor:innen

MSCNN–Transformer–PGA modelcapacitive coupling sensorlive monitoringpulse frequency response methodtransformer winding fault

Autor:innen und Institutionen

  • State Key Laboratory of Power Transmission Equipment Technology, Chongqing University, Chongqing 400044, China.

ORCID-Profile: Shoulong Dong

Zitieren

APA

Wang, Z., Zou, Y., Ma, J., Liu, Z., Peng, X., Zhang, T., Xiang, S., Yao, C., & Dong, S. (2026). Online Monitoring of Transformer Winding Faults Based on Pulse Coupling Injection. Sensors, 26(9), 2914. https://doi.org/10.3390/s26092914

Vancouver

Wang Z, Zou Y, Ma J, Liu Z, Peng X, Zhang T, et al. Online Monitoring of Transformer Winding Faults Based on Pulse Coupling Injection. Sensors. 2026;26(9):2914. doi:10.3390/s26092914

BibTeX
@article{Wang2026,
  author = {Wang, Zetong and Zou, Yuhan and Ma, Junhao and Liu, Zongnan and Peng, Xinyu and Zhang, Tianran and Xiang, Sizhe and Yao, Chenguo and Dong, Shoulong},
  title = {Online Monitoring of Transformer Winding Faults Based on Pulse Coupling Injection},
  journal = {Sensors},
  year = {2026},
  volume = {26},
  number = {9},
  pages = {2914},
  doi = {10.3390/s26092914}
}
Kostenlos starten →