Measurement System for Current Transformer Calibration from 50 Hz to 150 kHz Using a Wideband Power Analyzer

Mano Rom iD, Helko E van den Brom iD, Ernest Houtzager iD, Ronald van Leeuwen iD, Dennis van der Born iD, Gert Rietveld iD, Fabio Muñoz iD

Sensors · 02.09.2025 · 25 (17) · 5429

DOI: 10.3390/s25175429 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sensors, online erschienen am 02.09.2025. Verfasst von Mano Rom und 6 weiteren Autor:innen. Beteiligte Einrichtung: VSL B.V. (VSL), 2629 JA Delft, The Netherlands. Die Arbeit wurde bisher 12-mal zitiert (Crossref) und nennt 49 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: European Partnership on Metrology.

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Accurate and reliable characterization of current transformer (CT) performance is essential for maintaining grid stability and power quality in modern electrical networks. CT measurements are key to effective monitoring of harmonic distortions, supporting regulatory compliance and ensuring the safe operation of the grid. This paper addresses a method for the characterization of CTs across an extended frequency range from 50 Hz up to 150 kHz, driven by increasing power quality issues introduced by renewable energy installations and non-linear loads. Traditional CT calibration approaches involve measurement setups that offer ppm-level uncertainty but are complex to operate and limited in practical frequency range. To simplify and expand calibration capabilities, a calibration system employing a sampling ammeter (power analyzer) was developed, enabling the direct measurement of CT secondary currents of an unknown CT and a reference CT without any further auxiliary equipment. The resulting expanded magnitude ratio uncertainties for the wideband CT calibration system are 10 ppm (k=2) up to 10 kHz and less than 120 ppm from 10 kHz to 150 kHz; these uncertainties do not include the uncertainty of the reference CT. Additionally, the operational conditions and setup design choices, such as instrument warm-up duration, grounding methods, measurement shunt selection, and cable type, were evaluated for their impact on measurement uncertainty and repeatability. The results highlight the significance of minimizing parasitic impedances at higher frequencies and maintaining consistent testing conditions. The developed calibration setup provides a robust foundation for future standardization efforts and practical guidance to characterize CT performance in the increasingly important supraharmonic frequency range.

Schlagwörter

Stichwörter der Autor:innen

calibrationcurrent ratiocurrent transformersphase errorprecision power analyzersratio errorsampling current ratio bridgeuncertaintywide dynamic rangewideband

Autor:innen und Institutionen

  • VSL B.V. (VSL), 2629 JA Delft, The Netherlands.
  • Electrical Sustainable Energy Department, Delft University of Technology (TU Delft), 2628 CD Delft, The Netherlands.
  • Department of Electrical Engineering, Mathematics and Computer Science (EEMCS), University of Twente, 7522 NB Enschede, The Netherlands.

ORCID-Profile: Mano Rom, Helko E van den Brom, Ernest Houtzager, Ronald van Leeuwen, Dennis van der Born, Gert Rietveld, Fabio Muñoz

Förderung

  • European Partnership on Metrology

Zitieren

APA

Rom, M., van den Brom, H. E., Houtzager, E., van Leeuwen, R., van der Born, D., Rietveld, G., & Muñoz, F. (2025). Measurement System for Current Transformer Calibration from 50 Hz to 150 kHz Using a Wideband Power Analyzer. Sensors, 25(17), 5429. https://doi.org/10.3390/s25175429

Vancouver

Rom M, van den Brom HE, Houtzager E, van Leeuwen R, van der Born D, Rietveld G, et al. Measurement System for Current Transformer Calibration from 50 Hz to 150 kHz Using a Wideband Power Analyzer. Sensors. 2025;25(17):5429. doi:10.3390/s25175429

BibTeX
@article{Rom2025,
  author = {Rom, Mano and van den Brom, Helko E and Houtzager, Ernest and van Leeuwen, Ronald and van der Born, Dennis and Rietveld, Gert and Muñoz, Fabio},
  title = {Measurement System for Current Transformer Calibration from 50 Hz to 150 kHz Using a Wideband Power Analyzer},
  journal = {Sensors},
  year = {2025},
  volume = {25},
  number = {17},
  pages = {5429},
  doi = {10.3390/s25175429}
}
Kostenlos starten →