Detecting Partial Discharge in Cable Joints Based on Implanting Optical Fiber Using MZ–Sagnac Interferometry
Sensors · 17.05.2025 · 25 (10) · 3166
DOI: 10.3390/s25103166 ↗Kurz gefasst
Fachartikel in der Zeitschrift Sensors, online erschienen am 17.05.2025. Verfasst von Weikai Zhang und 7 weiteren Autor:innen. Beteiligte Einrichtung: State Key Laboratory of Power Transmission Equipment Technology, School of Electrical Engineering, Chongqing University, Chongqing 400044, China. Die Arbeit wurde bisher 14-mal zitiert (Crossref) und nennt 42 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: the Science & Technology Project of State Grid Corporation of China, Science & Technology Project of the State Grid Corporation of China, Hainan Provincial Natural Science Foundation of China.
Abstract (Originalsprache)
Detecting partial discharges in cable joints is critical for timely defect identification and reliable transmission system operation. To improve the long-term reliability and sensitivity of the sensing system, a novel method for cable joint monitoring based on implanting optical fibers within the joint structure is proposed. The electric field distribution of the optical fiber-implanted cable joint was simulated, followed by electrical performance tests, demonstrating that optical fiber implantation had a negligible effect on the electrical properties of the cable joint. A platform utilizing Mach–Zehnder–Sagnac (MZ–Sagnac) interferometry was developed to evaluate the frequency response of the implanted optical fiber sensor, with calibration performed on a non-standard curved surface. The results show that the average sensitivity of the sensor in the 10 kHz–80 kHz range is 71.6 dB, 2.0 dB higher than that of the piezoelectric transducer, with a maximum signal-to-noise ratio of 65.2 dB. To simulate common fault conditions in the actual operation of cable joints, four types of discharge defects were introduced. Partial discharge tests conducted on an optical fiber-implanted cable joint, supplemented by measurements using a partial discharge detector, demonstrate that the optical fiber sensors can detect a minimum discharge of 16.0 pC.
Schlagwörter
Stichwörter der Autor:innen
Autor:innen und Institutionen
- State Key Laboratory of Power Transmission Equipment Technology, School of Electrical Engineering, Chongqing University, Chongqing 400044, China.
- Shandong Taikai Cable Co., Ltd., Tai'an 271000, China.
- School of Mathematics and Statistics, Hainan University, Haikou 570228, China.
ORCID-Profile: Weikai Zhang
Förderung
- the Science & Technology Project of State Grid Corporation of China
- Science & Technology Project of the State Grid Corporation of China
- Hainan Provincial Natural Science Foundation of China
Zitieren
APA
Zhang, W., Song, Y., Wu, X., Liu, H., Tian, H., Tang, Z., Xu, S., & Chen, W. (2025). Detecting Partial Discharge in Cable Joints Based on Implanting Optical Fiber Using MZ–Sagnac Interferometry. Sensors, 25(10), 3166. https://doi.org/10.3390/s25103166
Vancouver
Zhang W, Song Y, Wu X, Liu H, Tian H, Tang Z, et al. Detecting Partial Discharge in Cable Joints Based on Implanting Optical Fiber Using MZ–Sagnac Interferometry. Sensors. 2025;25(10):3166. doi:10.3390/s25103166
BibTeX
@article{Zhang2025,
author = {Zhang, Weikai and Song, Yuxuan and Wu, Xiaowei and Liu, Hong and Tian, Haoyuan and Tang, Zijie and Xu, Shaopeng and Chen, Weigen},
title = {Detecting Partial Discharge in Cable Joints Based on Implanting Optical Fiber Using MZ–Sagnac Interferometry},
journal = {Sensors},
year = {2025},
volume = {25},
number = {10},
pages = {3166},
doi = {10.3390/s25103166}
}
EUVIMED