Diagnosis of Reverse-Connection Defects in High-Voltage Cable Cross-Bonded Grounding System Based on ARO-SVM
Sensors · 20.01.2025 · 25 (2) · 590
DOI: 10.3390/s25020590 ↗Kurz gefasst
Fachartikel in der Zeitschrift Sensors, online erschienen am 20.01.2025. Verfasst von Yuhao Ai und 5 weiteren Autor:innen. Beteiligte Einrichtung: Hubei Key Laboratory of Power Equipment & System Security for Integrated Energy, School of Electrical Engineering and Automation, Wuhan University, W…. Die Arbeit wurde bisher 7-mal zitiert (Crossref) und nennt 33 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
High-voltage (HV) cables are increasingly used in urban power grids, and their safe operation is critical to grid stability. Previous studies have analyzed various defects, including the open circuit in the sheath loop, the flooding in the cross-bonded link box, and the sheath grounding fault. However, there is a paucity of research on the defect of the reverse direction between the inner core and the outer shield of the coaxial cable. Firstly, this paper performed a theoretical analysis of the sheath current in the reversed-connection state and established a simulation model for verification. The outcomes of the simulation demonstrate that there are significant variations in the amplitudes of the sheath current under different reversed-connection conditions. Consequently, a feature vector was devised based on the amplitude of the sheath current. The support vector machine (SVM) was then applied to diagnose the reversed-connection defects in the HV cable cross-bonded grounding system. The artificial rabbits optimization (ARO) algorithm was adopted to optimize the SVM model, attaining an impressively high diagnostic accuracy rate of 99.35%. The effectiveness and feasibility of the proposed algorithm are confirmed through the analysis and validation of the practical example.
Schlagwörter
Stichwörter der Autor:innen
Autor:innen und Institutionen
- Hubei Key Laboratory of Power Equipment & System Security for Integrated Energy, School of Electrical Engineering and Automation, Wuhan University, Wuhan 430072, China.
- School of Electrical Engineering and Automation, Wuhan University, Wuhan 430072, China.
Zitieren
APA
Ai, Y., Song, B., Wu, S., Li, Y., Lu, L., & Wang, L. (2025). Diagnosis of Reverse-Connection Defects in High-Voltage Cable Cross-Bonded Grounding System Based on ARO-SVM. Sensors, 25(2), 590. https://doi.org/10.3390/s25020590
Vancouver
Ai Y, Song B, Wu S, Li Y, Lu L, Wang L. Diagnosis of Reverse-Connection Defects in High-Voltage Cable Cross-Bonded Grounding System Based on ARO-SVM. Sensors. 2025;25(2):590. doi:10.3390/s25020590
BibTeX
@article{Ai2025,
author = {Ai, Yuhao and Song, Bin and Wu, Shaocheng and Li, Yongwen and Lu, Li and Wang, Linong},
title = {Diagnosis of Reverse-Connection Defects in High-Voltage Cable Cross-Bonded Grounding System Based on ARO-SVM},
journal = {Sensors},
year = {2025},
volume = {25},
number = {2},
pages = {590},
doi = {10.3390/s25020590}
}
EUVIMED