High-Voltage Cable Buffer Layer Ablation Fault Identification Based on Artificial Intelligence and Frequency Domain Impedance Spectroscopy
Sensors · 11.05.2024 · 24 (10) · 3067
DOI: 10.3390/s24103067 ↗Kurz gefasst
Fachartikel in der Zeitschrift Sensors, online erschienen am 11.05.2024. Verfasst von Jiajun Liu und 3 weiteren Autor:innen. Beteiligte Einrichtung: School of Electrical Engineering, Xi'an University of Technology, Xi'an 710054, China. Die Arbeit wurde bisher 18-mal zitiert (Crossref) und nennt 26 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Natural Science Foundation of China, the Science and Technology Program of State Grid Shaanxi Electric Power Company.
Abstract (Originalsprache)
In recent years, the occurrence of high-voltage cable buffer layer ablation faults has become frequent, posing a serious threat to the safe and stable operation of cables. Failure to promptly detect and address such faults may lead to cable breakdowns, impacting the normal operation of the power system. To overcome the limitations of existing methods for identifying buffer layer ablation faults in high-voltage cables, a method for identifying buffer layer ablation faults based on frequency domain impedance spectroscopy and artificial intelligence is proposed. Firstly, based on the cable distributed parameter model and frequency domain impedance spectroscopy, a mathematical model of the input impedance of a cable containing buffer layer ablation faults is derived. Through a simulation, the input impedance spectroscopy at the first end of the cables under normal conditions, buffer layer ablation, local aging, and inductive faults is performed, enabling the identification of inductive and capacitive faults through a comparative analysis. Secondly, the frequency domain amplitude spectroscopy of the buffer layer ablation and local aging faults are used as datasets and are input into a neural network model for training and validation to identify buffer layer ablation and local aging faults. Finally, using multiple evaluation metrics to assess the neural network model validates the superiority of the MLP neural network in cable fault identification models and experimentally confirms the effectiveness of the proposed method.
Schlagwörter
Stichwörter der Autor:innen
Autor:innen und Institutionen
- School of Electrical Engineering, Xi'an University of Technology, Xi'an 710054, China.
Förderung
- Natural Science Foundation of China
- the Science and Technology Program of State Grid Shaanxi Electric Power Company
Zitieren
APA
Liu, J., Ma, M., Liu, X., & Xu, H. (2024). High-Voltage Cable Buffer Layer Ablation Fault Identification Based on Artificial Intelligence and Frequency Domain Impedance Spectroscopy. Sensors, 24(10), 3067. https://doi.org/10.3390/s24103067
Vancouver
Liu J, Ma M, Liu X, Xu H. High-Voltage Cable Buffer Layer Ablation Fault Identification Based on Artificial Intelligence and Frequency Domain Impedance Spectroscopy. Sensors. 2024;24(10):3067. doi:10.3390/s24103067
BibTeX
@article{Liu2024,
author = {Liu, Jiajun and Ma, Mingchao and Liu, Xin and Xu, Haokun},
title = {High-Voltage Cable Buffer Layer Ablation Fault Identification Based on Artificial Intelligence and Frequency Domain Impedance Spectroscopy},
journal = {Sensors},
year = {2024},
volume = {24},
number = {10},
pages = {3067},
doi = {10.3390/s24103067}
}