The Effects of Supraharmonic Distortion in MV and LV AC Grids
Sensors · 11.04.2024 · 24 (8) · 2465
DOI: 10.3390/s24082465 ↗Kurz gefasst
Fachartikel in der Zeitschrift Sensors, online erschienen am 11.04.2024. Verfasst von Andrea Mariscotti und 1 weiteren Autor:innen. Beteiligte Einrichtung: Department of Electrical, Electronic and Telecommunications Engineering, and Naval Architecture (DITEN), University of Genova, 16145 Genova, Italy. Die Arbeit wurde bisher 28-mal zitiert (Crossref) und nennt 98 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: European Association of National Metrology Institutes, European Partnership on Metrology.
Abstract (Originalsprache)
Since the integration of electronic devices and intelligent electronic devices into the power grid, power quality (PQ) has consistently remained a significant concern for system operators and experts. Maintaining high standards of power quality is crucial to preventing malfunctions and faults in electric assets and connected loads. Recently, PQ studies have shifted their focus to a specific frequency range, previously not considered problematic—the supraharmonic 2 kHz to 150 kHz range. This range is not populated by easily recognizable harmonic components of the 50 Hz to 60 Hz mains fundamental, but by a combination of intentional emissions, switching non-linearities and byproducts, and various types of resonances. This paper aims to provide a detailed analysis of the impact of supraharmonics (SHs) on power network operation and assets, focusing on the most relevant documented negative effects, namely power loss and the heating of grid elements, aging of dielectric materials, failure of medium voltage (MV) cable terminations, and interference with equipment and power line communication (PLC) technology in particular. Under some shareable assumptions, limits are derived and compared to existing ones for harmonic phenomena, providing a clear identification of the primary issues associated with supraharmonics and suggestions for the standardization process. Strictly related is the problem of grid monitoring and assessment of SH distortion, discussing the suitability of normative requirements for instrument transformers (ITs) with a specific focus on their accuracy.
Schlagwörter
Stichwörter der Autor:innen
Autor:innen und Institutionen
- Department of Electrical, Electronic and Telecommunications Engineering, and Naval Architecture (DITEN), University of Genova, 16145 Genova, Italy.
- Department of Electrical, Electronic, and Information Engineering (DEI), University of Bologna, 40136 Bologna, Italy.
ORCID-Profile: Andrea Mariscotti, Alessandro Mingotti
Förderung
- European Association of National Metrology Institutes
- European Partnership on Metrology
Zitieren
APA
Mariscotti, A., & Mingotti, A. (2024). The Effects of Supraharmonic Distortion in MV and LV AC Grids. Sensors, 24(8), 2465. https://doi.org/10.3390/s24082465
Vancouver
Mariscotti A, Mingotti A. The Effects of Supraharmonic Distortion in MV and LV AC Grids. Sensors. 2024;24(8):2465. doi:10.3390/s24082465
BibTeX
@article{Mariscotti2024,
author = {Mariscotti, Andrea and Mingotti, Alessandro},
title = {The Effects of Supraharmonic Distortion in MV and LV AC Grids},
journal = {Sensors},
year = {2024},
volume = {24},
number = {8},
pages = {2465},
doi = {10.3390/s24082465}
}