EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Diagnostics of Internal Defects in Composite Overhead Insulators Using an Optic E-Field Sensor

Damiano Fasani, Luca Barbieri iD, Andrea Villa iD, Daniele Palladini iD, Roberto Malgesini, Giovanni D'Avanzo iD, Giacomo Buccella, Paolo Gadia

Sensors · 20.02.2024 · 24 (5) · 1359

DOI: 10.3390/s24051359 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sensors, online erschienen am 20.02.2024. Verfasst von Damiano Fasani und 7 weiteren Autor:innen. Beteiligte Einrichtung: RSE SpA-Ricerca sul Sistema Energetico, Via Raffaele Rubattino, 54, 20134 Milano, Italy. Die Arbeit wurde bisher 3-mal zitiert (Crossref) und nennt 26 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Research Fund for the Italian Electrical System.

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Composite insulators for high-voltage overhead lines have better performances and are lighter than traditional designs, especially in heavily polluted areas. However, since it is a relatively recent technology, reliable methods to perform live-line diagnostics are still under development, especially with regard to internal defects, which provide few external symptoms. Thermal cameras can be employed, but their use is not always straightforward as the sun radiation can hide the thermal footprint of internal degenerative effects. In this work, an optical E-field sensor has been used to diagnose the internal defects of a set of composite insulators (bandwidth 200 mHz–50 MHz, min. detectable E-field 100 V/m). Moreover, a modelling activity using finite elements has been carried out to identify the possible nature of the defects by comparing experimental E-field profiles with those simulated assuming a specific defect geometry. The results show that the sensor can detect the presence of an internal defect, since its presence distorts the E-field profile when compared to the profile of a sound insulator. Moreover, the measured E-field profiles are compatible with the corresponding simulated ones when a conductive defect is considered. However, it was observed that a defect whose conductivity is not at least two orders of magnitude greater than the conductivity of the surroundings remains undetected.

Schlagwörter

Stichwörter der Autor:innen

composite insulatorelectro-optic sensorlive-line diagnostics

Autor:innen und Institutionen

  • RSE SpA-Ricerca sul Sistema Energetico, Via Raffaele Rubattino, 54, 20134 Milano, Italy.

ORCID-Profile: Luca Barbieri, Andrea Villa, Daniele Palladini, Giovanni D'Avanzo

Förderung

  • Research Fund for the Italian Electrical System

Zitieren

APA

Fasani, D., Barbieri, L., Villa, A., Palladini, D., Malgesini, R., D'Avanzo, G., Buccella, G., & Gadia, P. (2024). Diagnostics of Internal Defects in Composite Overhead Insulators Using an Optic E-Field Sensor. Sensors, 24(5), 1359. https://doi.org/10.3390/s24051359

Vancouver

Fasani D, Barbieri L, Villa A, Palladini D, Malgesini R, D'Avanzo G, et al. Diagnostics of Internal Defects in Composite Overhead Insulators Using an Optic E-Field Sensor. Sensors. 2024;24(5):1359. doi:10.3390/s24051359

BibTeX
@article{Fasani2024,
  author = {Fasani, Damiano and Barbieri, Luca and Villa, Andrea and Palladini, Daniele and Malgesini, Roberto and D'Avanzo, Giovanni and Buccella, Giacomo and Gadia, Paolo},
  title = {Diagnostics of Internal Defects in Composite Overhead Insulators Using an Optic E-Field Sensor},
  journal = {Sensors},
  year = {2024},
  volume = {24},
  number = {5},
  pages = {1359},
  doi = {10.3390/s24051359}
}