EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Characterization of Instrument Transformers under Realistic Conditions: Impact of Single and Combined Influence Quantities on Their Wideband Behavior

Palma Sara Letizia, Gabriella Crotti, Alessandro Mingotti iD, Roberto Tinarelli iD, Yeying Chen iD, Enrico Mohns iD, Mohamed Agazar iD, Daniela Istrate iD, Burak Ayhan iD, Hüseyin Çayci, Robert Stiegler iD

Sensors · 12.09.2023 · 23 (18) · 7833

DOI: 10.3390/s23187833 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sensors, online erschienen am 12.09.2023. Verfasst von Palma Sara Letizia und 10 weiteren Autor:innen. Beteiligte Einrichtung: Istituto Nazionale di Ricerca Metrologica (INRIM), Strada delle Cacce 91, 10135 Torino, Italy. Die Arbeit wurde bisher 30-mal zitiert (Crossref) und nennt 40 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: EMPIR programme co-financed by the Participating States and from the European Union's Horizon 2020 research and innovation programme., EMPIR programme.

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Instrument transformers (ITs) play a key role in electrical power systems, facilitating the accurate monitoring and measurement of electrical quantities. They are essential for measurement, protection, and metering in transmission and distribution grids and accurately reducing the grid voltage and current for low-voltage input instrumentation. With the increase in renewable energy sources, electronic converters, and electric vehicles connected to power grids, ITs now face challenging distorted conditions that differ from the nominal ones. The study presented in this paper is a collaborative work between national metrology institutes and universities that analyzes IT performance in measuring distorted voltages and currents in medium-voltage grids under realistic conditions. Both current and voltage measuring transformers are examined, considering influence quantities like the temperature, mechanical vibration, burden, adjacent phases, and proximity effects. The study provides detailed insights into measurement setups and procedures, and it quantifies potential errors arising from IT behavior in measuring distorted signals in the presence of the various considered influence quantities and their combinations. The main findings reveal that the temperature has the most evident impact on the inductive voltage transformer performance, as well as the burden, causing significant changes in ratio error and phase displacement at the lower temperatures. As for low-power ITs, establishing a priori the effects of adjacent phases and proximity on the frequency responses of low-power ITs is a complex matter, because of their different characteristics and construction solutions.

Schlagwörter

Stichwörter der Autor:innen

accuracydistribution gridsharmonicsinfluence quantityinstrument transformersmeasurement traceabilitypower quality

Autor:innen und Institutionen

  • Istituto Nazionale di Ricerca Metrologica (INRIM), Strada delle Cacce 91, 10135 Torino, Italy.
  • Department of Electrical, Electronic and Information Engineering, Guglielmo Marconi, Alma Mater Studiorum, University of Bologna, Viale del Risorgimento 2, 40136 Bologna, Italy.
  • Department 2.3-Electrical Energy Measuring Techniques, Physikalisch-Technische Bundesanstalt (PTB), Bundesallee 100, 38116 Braunschweig, Germany.
  • Laboratoire National de Métrologie et d'Essais (LNE), 1 Rue Gaston Boissier, 75015 Paris, France.
  • Power and Energy Laboratory, TÜBİTAK National Metrology Institute, 41470 Gebze, Kocaeli, Türkiye.
  • Institute of Electrical Power Systems and High Voltage Engineering, TUD Dresden University of Technology, 01062 Dresden, Germany.

ORCID-Profile: Alessandro Mingotti, Roberto Tinarelli, Yeying Chen, Enrico Mohns, Mohamed Agazar, Daniela Istrate, Burak Ayhan, Robert Stiegler

Förderung

  • EMPIR programme co-financed by the Participating States and from the European Union's Horizon 2020 research and innovation programme.
  • EMPIR programme

Zitieren

APA

Letizia, P. S., Crotti, G., Mingotti, A., Tinarelli, R., Chen, Y., Mohns, E., Agazar, M., Istrate, D., Ayhan, B., Çayci, H., & Stiegler, R. (2023). Characterization of Instrument Transformers under Realistic Conditions: Impact of Single and Combined Influence Quantities on Their Wideband Behavior. Sensors, 23(18), 7833. https://doi.org/10.3390/s23187833

Vancouver

Letizia PS, Crotti G, Mingotti A, Tinarelli R, Chen Y, Mohns E, et al. Characterization of Instrument Transformers under Realistic Conditions: Impact of Single and Combined Influence Quantities on Their Wideband Behavior. Sensors. 2023;23(18):7833. doi:10.3390/s23187833

BibTeX
@article{Letizia2023,
  author = {Letizia, Palma Sara and Crotti, Gabriella and Mingotti, Alessandro and Tinarelli, Roberto and Chen, Yeying and Mohns, Enrico and Agazar, Mohamed and Istrate, Daniela and Ayhan, Burak and Çayci, Hüseyin and Stiegler, Robert},
  title = {Characterization of Instrument Transformers under Realistic Conditions: Impact of Single and Combined Influence Quantities on Their Wideband Behavior},
  journal = {Sensors},
  year = {2023},
  volume = {23},
  number = {18},
  pages = {7833},
  doi = {10.3390/s23187833}
}
Kostenlos starten →