Gas-Generation Characteristics of Mineral Oil, Natural Ester and Synthetic Ester Under Multiple Partial-Discharge Regimes: Implications for Dissolved Gas Analysis
Processes · 20.11.2026 · 14 (22) · 3731
DOI: 10.3390/pr14223731 ↗Kurz gefasst
Fachartikel in der Zeitschrift Processes, online erschienen am 20.11.2026. Verfasst von Xuelei Wang und 4 weiteren Autor:innen. Die Arbeit nennt 29 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Shandong Electric Power Company, State Key Laboratory of Electric Insulation and Power Equipment, Xi’an Jiaotong University.
Abstract (Originalsprache)
Partial discharge (PD) is a major cause of insulation degradation in oil-immersed power equipment, and dissolved-gas analysis (DGA) is the principal chemical diagnostic tool for such faults; conventional DGA criteria, however, were developed for mineral oil and may not transfer directly to ester-based insulating liquids. The gas-generation characteristics of mineral oil (Kunlun KI50X), natural ester (FR3) and synthetic ester (MIDEL 7131) were investigated under four representative PD regimes: corona, surface, cavity and floating-electrode discharge, with insulating pressboard present; the corona configuration was tested additionally without pressboard, and all configurations were further examined under higher-energy spark discharge, on a closed-loop oil-circulation platform combining synchronized phase-resolved PD (PRPD) monitoring with automatic oil chromatography. Under moderate-energy PD, mineral oil produces mainly H2 together with the hydrocarbon gases CH4 and C2H2, whereas both esters preferentially liberate H2 and CO, reflecting their ester linkages; the presence of pressboard further elevates CO/CO2 through cellulose decomposition. Under intermittent sparking, the C2H2 and H2 production rates converge across the three fluids, indicating that molecular-structure effects diminish once repeated dielectric breakdown occurs. Within each PD mode, estimated cumulative discharge energy and cumulative dissolved-gas volume are linearly related, but this linearity deteriorates when data from different modes are pooled. Conventional mineral oil DGA schemes therefore cannot be applied uncritically to ester-filled apparatus; reliable fault diagnosis requires combined electrical (PRPD-based energy quantification) and oil-specific chemical (DGA) diagnostics.
Förderung
- Shandong Electric Power Company
- State Key Laboratory of Electric Insulation and Power Equipment, Xi’an Jiaotong University
Zitieren
APA
Wang, X., Zhu, W., Song, J., He, J., & Wu, Z. (2026). Gas-Generation Characteristics of Mineral Oil, Natural Ester and Synthetic Ester Under Multiple Partial-Discharge Regimes: Implications for Dissolved Gas Analysis. Processes, 14(22), 3731. https://doi.org/10.3390/pr14223731
Vancouver
Wang X, Zhu W, Song J, He J, Wu Z. Gas-Generation Characteristics of Mineral Oil, Natural Ester and Synthetic Ester Under Multiple Partial-Discharge Regimes: Implications for Dissolved Gas Analysis. Processes. 2026;14(22):3731. doi:10.3390/pr14223731
BibTeX
@article{Wang2026,
author = {Wang, Xuelei and Zhu, Wenbing and Song, Jinxuan and He, Jinyang and Wu, Zhicheng},
title = {Gas-Generation Characteristics of Mineral Oil, Natural Ester and Synthetic Ester Under Multiple Partial-Discharge Regimes: Implications for Dissolved Gas Analysis},
journal = {Processes},
year = {2026},
volume = {14},
number = {22},
pages = {3731},
doi = {10.3390/pr14223731}
}
EUVIMED