Quantification of Regional Thermal Responses and Zone-Wise Radiant-Tube Power Redistribution in an Industrial Continuous Annealing Furnace
Processes · 12.11.2026 · 14 (22) · 3658
DOI: 10.3390/pr14223658 ↗Kurz gefasst
Fachartikel in der Zeitschrift Processes, online erschienen am 12.11.2026. Verfasst von Jiamin Sun und 4 weiteren Autor:innen. Die Arbeit nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
Industrial continuous annealing furnaces contain numerous distributed radiant tubes operated through existing control regions. This study proposes a zone-wise radiant-tube power redistribution method based on quantified regional thermal responses. A three-dimensional thermal-process model was established under actual industrial operating conditions and evaluated against the measured strip outlet temperature. The simulated outlet temperature was 806.52 °C, compared with an industrial measurement of 801 °C, corresponding to a relative deviation of 0.69%. The model followed the eight existing control regions, P1–P8. Reducing the power of each tube in one region at a time by 10 kW produced outlet-temperature decreases of 6.56, 4.60, 3.74, 3.73, and 1.80 °C for P2–P6, respectively. These values describe the overall responses to the prescribed regional control actions. Guided by these responses, candidate zone-wise power configurations were screened using a maximum simulated outlet-temperature decrease of 2 °C from the baseline and the fuel-saving ratio as the energy metric. The selected configuration yielded a simulated outlet temperature of 804.55 °C and an estimated fuel-saving ratio of 1.17% relative to the historical baseline under the specified fuel-conversion conditions. The proposed method evaluates power configurations within the existing furnace control regions and provides an engineering-feasible approach for energy-efficient furnace operation without modifying the furnace structure or fundamental heating mode.
Zitieren
APA
Sun, J., Wang, Q., Wang, H., Ge, C., & Zhang, X. (2026). Quantification of Regional Thermal Responses and Zone-Wise Radiant-Tube Power Redistribution in an Industrial Continuous Annealing Furnace. Processes, 14(22), 3658. https://doi.org/10.3390/pr14223658
Vancouver
Sun J, Wang Q, Wang H, Ge C, Zhang X. Quantification of Regional Thermal Responses and Zone-Wise Radiant-Tube Power Redistribution in an Industrial Continuous Annealing Furnace. Processes. 2026;14(22):3658. doi:10.3390/pr14223658
BibTeX
@article{Sun2026,
author = {Sun, Jiamin and Wang, Quan and Wang, Hongbin and Ge, Chenyu and Zhang, Xianxu},
title = {Quantification of Regional Thermal Responses and Zone-Wise Radiant-Tube Power Redistribution in an Industrial Continuous Annealing Furnace},
journal = {Processes},
year = {2026},
volume = {14},
number = {22},
pages = {3658},
doi = {10.3390/pr14223658}
}
EUVIMED