Adaptive Distance Protection Setting Method Based on Sensitivity Constraints and Disturbance-Domain Model
Processes · 27.05.2026 · 14 (11) · 1752
DOI: 10.3390/pr14111752 ↗Kurz gefasst
Fachartikel in der Zeitschrift Processes, online erschienen am 27.05.2026. Verfasst von Jianbin Ci und 8 weiteren Autor:innen. Die Arbeit nennt 13 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: State Grid Corporation of China Technology Project.
Abstract (Originalsprache)
With the expansion of transmission networks and the increasing penetration of inverter-based resources (IBRs), fixed offline distance-protection settings face increasing difficulty in balancing selectivity, sensitivity, and operating speed. This problem is particularly evident in Zone III remote-backup protection, where conservative load-avoidance settings may create blind zones. This paper proposes an adaptive three-zone distance-protection setting method based on explicit sensitivity constraints and a disturbance-domain model. The method has two main features. First, online recalculation is restricted to the local disturbance domain affected by topology changes, thereby avoiding network-wide recomputation. Second, Zone II and Zone III settings are determined by a constrained model that incorporates real-time branch coefficients, load impedance, sensitivity requirements, and downstream coordination limits. A fallback mechanism is also included to maintain security under data loss or abnormal measurements. In a 220 kV case study, the proposed method increases the Zone II sensitivity coefficient from 1.92 to 1.95 and the Zone III remote-backup sensitivity coefficient from 0.83 to 1.35. Additional tests under high-resistance faults, measurement errors, volatile load, and inverter-based resource integration show that the method preserves selectivity while reducing backup protection blind zones. The disturbance-domain strategy also reduces the average recalculation time from 820 ms to 18 ms in the tested regional setting-calculation scenario.
Förderung
- State Grid Corporation of China Technology Project
Zitieren
APA
Ci, J., Yu, Y., Li, T., Sun, Z., Tian, J., Dong, M., Ma, Q., Wang, S., & Mo, J. (2026). Adaptive Distance Protection Setting Method Based on Sensitivity Constraints and Disturbance-Domain Model. Processes, 14(11), 1752. https://doi.org/10.3390/pr14111752
Vancouver
Ci J, Yu Y, Li T, Sun Z, Tian J, Dong M, et al. Adaptive Distance Protection Setting Method Based on Sensitivity Constraints and Disturbance-Domain Model. Processes. 2026;14(11):1752. doi:10.3390/pr14111752
BibTeX
@article{Ci2026,
author = {Ci, Jianbin and Yu, You and Li, Tao and Sun, Zhenting and Tian, Jingfu and Dong, Ming and Ma, Qiang and Wang, Shiming and Mo, Jingshan},
title = {Adaptive Distance Protection Setting Method Based on Sensitivity Constraints and Disturbance-Domain Model},
journal = {Processes},
year = {2026},
volume = {14},
number = {11},
pages = {1752},
doi = {10.3390/pr14111752}
}
EUVIMED