Simulation and Performance Evaluation of Trans-Critical CO2 Refrigeration System Integrated with Spray-Cooled Gas Coolers
Processes · 12.03.2026 · 14 (6) · 903
DOI: 10.3390/pr14060903 ↗Kurz gefasst
Fachartikel in der Zeitschrift Processes, online erschienen am 12.03.2026. Verfasst von Lei Chai und 2 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 31 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Engineering and Physical Sciences Research Council (EPSRC) of the UK, European Union’s Horizon 2020 research and innovation program, Brunel Research Culture Seed Fund.
Abstract (Originalsprache)
Rising ambient temperatures pose significant challenges to the thermodynamic performance of trans-critical CO2 refrigeration systems, as they reduce system efficiency and cooling capacity. To mitigate these adverse effects, a spray-cooling technique was employed to enhance the heat rejection process. A mathematical model of the spray-cooled gas cooler, employing a homogeneous-mixture assumption that treats air and water droplets as a single phase without velocity slip or temperature difference, was developed and validated against experimental data. The developed model was subsequently integrated into the refrigeration system model to evaluate the system’s performance with an air temperature range of 30 °C to 40 °C. The results show that spray cooling effectively decreases the CO2 pressure and temperature exiting the gas cooler, lowers the compressor power consumption, enhances the evaporator cooling capacity, and significantly improves the overall system performance. The results also indicate that increasing the spray-water-to-air-mass flow rate ratio beyond around 0.075 yields negligible gains. Under conditions of air temperature of 40 °C, air velocity of 2 m/s and spray-water temperature of 25 °C, the coefficient of performance increased from 1.53 to 2.74, the heat rejection rate rose by 9.8%, the cooling capacity improved by 33.3%, and the compressor power consumption decreased by 25.9% as the spray-water-to-air-mass flow rate ratio increased from 0.02 to 0.075.
Förderung
- Engineering and Physical Sciences Research Council (EPSRC) of the UK
- European Union’s Horizon 2020 research and innovation program
- Brunel Research Culture Seed Fund
Zitieren
APA
Chai, L., Tassou, S. A., & Tsamos, K. M. (2026). Simulation and Performance Evaluation of Trans-Critical CO2 Refrigeration System Integrated with Spray-Cooled Gas Coolers. Processes, 14(6), 903. https://doi.org/10.3390/pr14060903
Vancouver
Chai L, Tassou SA, Tsamos KM. Simulation and Performance Evaluation of Trans-Critical CO2 Refrigeration System Integrated with Spray-Cooled Gas Coolers. Processes. 2026;14(6):903. doi:10.3390/pr14060903
BibTeX
@article{Chai2026,
author = {Chai, Lei and Tassou, Savvas A. and Tsamos, Konstantinos M.},
title = {Simulation and Performance Evaluation of Trans-Critical CO2 Refrigeration System Integrated with Spray-Cooled Gas Coolers},
journal = {Processes},
year = {2026},
volume = {14},
number = {6},
pages = {903},
doi = {10.3390/pr14060903}
}
EUVIMED