EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

High-Pressure Fine Water Mist Nozzle Retrofit Experiment and Numerical Simulation Study

Xin-Zhi Yang, Chen-Yang Du, Yuan-Jun Liu, Yan Tang, Xi-Lin Dong, An-Chi Huang

Processes · 24.02.2025 · 13 (3) · 642

DOI: 10.3390/pr13030642 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Processes, online erschienen am 24.02.2025. Verfasst von Xin-Zhi Yang und 5 weiteren Autor:innen. Die Arbeit wurde bisher 6-mal zitiert (Crossref) und nennt 41 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Key Research Development Program of China, CNPC-CZU Innovation Alliance, National Natural Science Foundation of China, Lunghwa University of Science and Technology Open Training Project.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Currently, the existing high-pressure water mist fire protection systems in cold storage facilities face challenges in achieving efficient atomization and uniform water mist distribution, which may limit their effectiveness in rapid cooling and flame suppression. The objective of this investigation is to improve the performance of high-pressure fine water mist nozzles by integrating a Venturi microbubble generator to improve mist atomization and distribution, particularly in the context of flames involving combustible polyurethane foam insulation materials. The gas–liquid two-phase flow characteristics within Venturi tubes were investigated through numerical simulations using ANSYS-Fluent 2022 R1 software. This study focused on critical parameters, including the water inlet pressure (1–9 MPa), pharynx diameter (8–12 mm), contraction angle (15–45°), and expansion angle (15–45°). The average water mist droplet diameters at 1, 3, and 9 MPa were 169.890, 150.002, and 115.606 μm, respectively, in the absence of the Venturi tube, according to the experimental results. A reduction of up to 16.7% was achieved by reducing the particulate sizes to 141.462, 139.142, and 109.525 μm using the Venturi tube. The fire-extinguishing time and water consumption were substantially reduced at higher pressures, such as 9 MPa. Under high-pressure conditions, the results indicated that the Venturi microbubble technology was significantly more effective in suppressing fires. The novelty of this study lies in the application of Venturi microbubble technology to improve fine water mist systems for fire protection in cold storage facilities. This enhanced system achieves better atomization, uniform water mist distribution, faster cooling, and more efficient flame suppression, making it a viable solution for improving fire protection in such environments.

Förderung

  • National Key Research Development Program of China
  • CNPC-CZU Innovation Alliance, National Natural Science Foundation of China
  • Lunghwa University of Science and Technology Open Training Project

Zitieren

APA

Yang, X., Du, C., Liu, Y., Tang, Y., Dong, X., & Huang, A. (2025). High-Pressure Fine Water Mist Nozzle Retrofit Experiment and Numerical Simulation Study. Processes, 13(3), 642. https://doi.org/10.3390/pr13030642

Vancouver

Yang X, Du C, Liu Y, Tang Y, Dong X, Huang A. High-Pressure Fine Water Mist Nozzle Retrofit Experiment and Numerical Simulation Study. Processes. 2025;13(3):642. doi:10.3390/pr13030642

BibTeX
@article{Yang2025,
  author = {Yang, Xin-Zhi and Du, Chen-Yang and Liu, Yuan-Jun and Tang, Yan and Dong, Xi-Lin and Huang, An-Chi},
  title = {High-Pressure Fine Water Mist Nozzle Retrofit Experiment and Numerical Simulation Study},
  journal = {Processes},
  year = {2025},
  volume = {13},
  number = {3},
  pages = {642},
  doi = {10.3390/pr13030642}
}
Kostenlos starten →