Low-Power Chemiresistive Gas Sensors for Transformer Fault Diagnosis
Molecules · 29.09.2024 · 29 (19) · 4625
DOI: 10.3390/molecules29194625 ↗Kurz gefasst
Übersichtsarbeit in der Zeitschrift Molecules, online erschienen am 29.09.2024. Verfasst von Haixia Mei und 3 weiteren Autor:innen. Beteiligte Einrichtung: Key Lab Intelligent Rehabil & Barrier free Disable (Ministry of Education), Changchun University, Changchun 130022, China. Die Arbeit wurde bisher 18-mal zitiert (Crossref) und nennt 137 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Natural Science Foundation of China, China Postdoctoral Science Foundation, ilin Provincial Department of Education.
Abstract (Originalsprache)
Dissolved gas analysis (DGA) is considered to be the most convenient and effective approach for transformer fault diagnosis. Due to their excellent performance and development potential, chemiresistive gas sensors are anticipated to supersede the traditional gas chromatography analysis in the dissolved gas analysis of transformers. However, their high operating temperature and high power consumption restrict their deployment in battery-powered devices. This review examines the underlying principles of chemiresistive gas sensors. It comprehensively summarizes recent advances in low-power gas sensors for the detection of dissolved fault characteristic gases (H2, C2H2, CH4, C2H6, C2H4, CO, and CO2). Emphasis is placed on the synthesis methods of sensitive materials and their properties. The investigations have yielded substantial experimental data, indicating that adjusting the particle size and morphology structure of the sensitive materials and combining them with noble metal doping are the principal methods for enhancing the sensitivity performance and reducing the power consumption of chemiresistive gas sensors. Additionally, strategies to overcome the significant challenge of cross-sensitivity encountered in applications are provided. Finally, the future development direction of chemiresistive gas sensors for DGA is envisioned, offering guidance for developing and applying novel gas-sensitive sensors in transformer fault diagnosis.
Schlagwörter
Stichwörter der Autor:innen
Autor:innen und Institutionen
- Key Lab Intelligent Rehabil & Barrier free Disable (Ministry of Education), Changchun University, Changchun 130022, China.
- Shanghai Key Laboratory of Intelligent Sensing and Detection Technology, School of Mechanical and Power Engineering, East China University of Science and Technology, Shanghai 200237, China.
ORCID-Profile: Haixia Mei, Tao Wang
Förderung
- National Natural Science Foundation of China
- China Postdoctoral Science Foundation
- ilin Provincial Department of Education
- China Southern Power Grid Limited Liability Company Technology Project
- Jilin Provincial Department of Education
Zitieren
APA
Mei, H., Peng, J., Xu, D., & Wang, T. (2024). Low-Power Chemiresistive Gas Sensors for Transformer Fault Diagnosis. Molecules, 29(19), 4625. https://doi.org/10.3390/molecules29194625
Vancouver
Mei H, Peng J, Xu D, Wang T. Low-Power Chemiresistive Gas Sensors for Transformer Fault Diagnosis. Molecules. 2024;29(19):4625. doi:10.3390/molecules29194625
BibTeX
@article{Mei2024,
author = {Mei, Haixia and Peng, Jingyi and Xu, Dongdong and Wang, Tao},
title = {Low-Power Chemiresistive Gas Sensors for Transformer Fault Diagnosis},
journal = {Molecules},
year = {2024},
volume = {29},
number = {19},
pages = {4625},
doi = {10.3390/molecules29194625}
}
EUVIMED