Premature Failure of Galvanized Fire Sprinkler Pipes in Coastal Conditions: Evidence of Sequential Atmospheric and Aqueous Corrosion
Materials · 02.06.2026 · 19 (11) · 2360
DOI: 10.3390/ma19112360 ↗Kurz gefasst
Fachartikel in der Zeitschrift Materials, online erschienen am 02.06.2026. Verfasst von Oz Golan und 2 weiteren Autor:innen. Beteiligte Einrichtung: Afeka Center for Materials and Process Engineering, Afeka Tel-Aviv Academic College of Engineering, Tel Aviv 6998812, Israel. Die Arbeit nennt 25 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Israel Science Foundation.
Abstract (Originalsprache)
This case study investigates the rapid through-wall perforation of newly installed hot-dip galvanized (HDG) fire sprinkler pipes in a coastal Mediterranean environment. Failure occurred along the internal waterline of horizontal sections within a short service period. Forensic analysis—comprising metallography, SEM, and EDS—identified a synergistic atmospheric–aqueous corrosion mechanism. Marine aerosol exposure during pre-service storage led to significant chloride enrichment and localized depletion of the 40–50 μm zinc coating, initiating early-stage pitting. Upon commissioning, stagnant water established oxygen concentration gradients and differential-aeration cells, driving localized anodic dissolution. Additionally, sulfate-reducing bacteria (SRB) contributed to accelerated degradation through microbiologically influenced corrosion (MIC), as suggested by sulfur-bearing tubercles. The findings demonstrate that standard galvanizing thickness alone does not ensure longevity in high-salinity environments if atmospheric “preconditioning” occurs. These results underscore the necessity of shielding internal pipe surfaces during storage and construction to prevent premature failure. This case study informs predictive maintenance and material selection for stagnant-water systems in coastal regions.
Schlagwörter
Stichwörter der Autor:innen
Autor:innen und Institutionen
- Afeka Center for Materials and Process Engineering, Afeka Tel-Aviv Academic College of Engineering, Tel Aviv 6998812, Israel.
- Scojen Institute for Synthetic Biology, Reichman University, Herzliya 4610101, Israel.
ORCID-Profile: Oz Golan, Ilana Kolodkin-Gal
Förderung
- Israel Science Foundation
Zitieren
APA
Golan, O., Pasternak, A., & Kolodkin-Gal, I. (2026). Premature Failure of Galvanized Fire Sprinkler Pipes in Coastal Conditions: Evidence of Sequential Atmospheric and Aqueous Corrosion. Materials, 19(11), 2360. https://doi.org/10.3390/ma19112360
Vancouver
Golan O, Pasternak A, Kolodkin-Gal I. Premature Failure of Galvanized Fire Sprinkler Pipes in Coastal Conditions: Evidence of Sequential Atmospheric and Aqueous Corrosion. Materials. 2026;19(11):2360. doi:10.3390/ma19112360
BibTeX
@article{Golan2026,
author = {Golan, Oz and Pasternak, Avraham and Kolodkin-Gal, Ilana},
title = {Premature Failure of Galvanized Fire Sprinkler Pipes in Coastal Conditions: Evidence of Sequential Atmospheric and Aqueous Corrosion},
journal = {Materials},
year = {2026},
volume = {19},
number = {11},
pages = {2360},
doi = {10.3390/ma19112360}
}