The Failure of Voltage Divider Induced by Insulating Material Degradation Under Coupling Effect of High-Frequency Field and Temperature
Materials · 14.05.2026 · 19 (10) · 2047
DOI: 10.3390/ma19102047 ↗Kurz gefasst
Fachartikel in der Zeitschrift Materials, online erschienen am 14.05.2026. Verfasst von Xuan Li und 7 weiteren Autor:innen. Beteiligte Einrichtung: Equipment Management Department of State Grid Corporation of China, Beijing 100032, China. Die Arbeit nennt 38 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Headquarters' Science and Technology Project of State Grid Corporation of China (Ascent Plan), Headquarters’ Science and Technology Project of State Grid Corporation of China.
Abstract (Originalsprache)
This paper systematically investigates the failure characteristics and mechanisms of insulating materials in DC voltage dividers under combined high-frequency voltage and high-temperature conditions via simulations and experiments. The results showed that high-frequency harmonics severely degrade the insulation strength of polypropylene/paper/polypropylene (PPLP) at 10 kHz, in which the bulk breakdown strength of PPLP decreases by over 50%. Furthermore, the surface flashover voltage in oil is reduced by 17.7% under high-frequency voltage alone, and by as much as 51% when white flocculent substances are present in the oil. The dielectric properties of PPLP strongly depend on frequency and temperature, which aggravate the heat accumulation of the divider under high-frequency voltage. Furthermore, the multilayer structure of PPLP introduces deeper trap levels due to interfacial states, which reduce the breakdown strength and flashover voltage of PPLP. Electro-thermal coupling induces a rapid temperature rising to 98 °C at 25 kHz caused by dielectric loss, leading to oil turbidity and white precipitation, consistent with finite element simulations. Consequently, a failure mechanism is proposed as follows: prolonged electro-thermal stress causes chain scission in styrene-containing materials, releasing monomers that repolymerize into white polystyrene deposits. Their porous structure and dielectric mismatch distort the interfacial field, trigger partial discharge, and aggravate surface flashover.
Schlagwörter
Stichwörter der Autor:innen
Autor:innen und Institutionen
- Equipment Management Department of State Grid Corporation of China, Beijing 100032, China.
- School of Electrical Engineering, Xi'an Jiaotong University, Xi'an 710049, China.
- State Grid Economic and Technological Research Institute Co., Ltd., Beijing 102200, China.
- State Grid Hubei Electric Power Co., Ltd., Wuhan 430048, China.
Förderung
- Headquarters' Science and Technology Project of State Grid Corporation of China (Ascent Plan)
- Headquarters’ Science and Technology Project of State Grid Corporation of China
Zitieren
APA
Li, X., Zhang, C., Liu, Z., Song, J., Tian, H., Xie, Q., Zhang, Z., & Li, S. (2026). The Failure of Voltage Divider Induced by Insulating Material Degradation Under Coupling Effect of High-Frequency Field and Temperature. Materials, 19(10), 2047. https://doi.org/10.3390/ma19102047
Vancouver
Li X, Zhang C, Liu Z, Song J, Tian H, Xie Q, et al. The Failure of Voltage Divider Induced by Insulating Material Degradation Under Coupling Effect of High-Frequency Field and Temperature. Materials. 2026;19(10):2047. doi:10.3390/ma19102047
BibTeX
@article{Li2026,
author = {Li, Xuan and Zhang, Chuang and Liu, Zixi and Song, Jiajie and Tian, Huidong and Xie, Qijia and Zhang, Zhengmao and Li, Shengtao},
title = {The Failure of Voltage Divider Induced by Insulating Material Degradation Under Coupling Effect of High-Frequency Field and Temperature},
journal = {Materials},
year = {2026},
volume = {19},
number = {10},
pages = {2047},
doi = {10.3390/ma19102047}
}
EUVIMED