EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Fault Diagnosis of Natural Ester Oil Filled Transformers Using Mechanism Inspired Structured Tokens and Auxiliary Supervision with Full Window Trends

Chengfei Zhang, Mingze Sun, Zhan Cao, Xiangzhuo Kong, Man Ding

Inventions · 23.11.2026 · 11 (6) · 131

DOI: 10.3390/inventions11060131 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Inventions, online erschienen am 23.11.2026. Verfasst von Chengfei Zhang und 4 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Construction Branch of State Grid Jiangsu Electric Power Co., Ltd..

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The pursuit of carbon peaking and carbon neutrality has increased demand for environmentally friendly natural ester oil-filled transformers. Abnormal dissolved gas levels can compromise their operational reliability, making dissolved gas analysis (DGA) and fault diagnosis essential to stable operation. This study proposes a three-class diagnostic method that integrates mechanism-inspired structured tokens, a full-window trend residual, and auxiliary supervision of thermal and discharge components to diagnose thermal, discharge, and combined electrical–thermal faults in natural ester oil-filled transformers. Using 900 training sequences and 120 test sequences, with 0 min as the normal baseline and evaluation at 10–60 min, the method achieved mean accuracies of 93.47% and 93.19% at 20 and 30 min, respectively, across six runs. These values exceeded those of the model without auxiliary supervision using the same observation window by 0.56 and 1.25 percentage points. The benefits of auxiliary supervision were not observed at every diagnostic time point. In a fixed reference run, the accuracies at successive time points were 95.83%, 95.83%, 93.33%, 92.50%, 90.00%, and 87.50%. At later time points, missed combined faults were predominantly classified as discharge faults, whereas all 40 discharge-fault sequences were correctly identified at every time point. The study provides a theoretical basis and technical support for DGA-based diagnosis of natural ester oil-filled transformers and may contribute to their operational stability. However, generalization across experimental batches and the benefits of component-level supervision require further validation.

Förderung

  • Construction Branch of State Grid Jiangsu Electric Power Co., Ltd.

Zitieren

APA

Zhang, C., Sun, M., Cao, Z., Kong, X., & Ding, M. (2026). Fault Diagnosis of Natural Ester Oil Filled Transformers Using Mechanism Inspired Structured Tokens and Auxiliary Supervision with Full Window Trends. Inventions, 11(6), 131. https://doi.org/10.3390/inventions11060131

Vancouver

Zhang C, Sun M, Cao Z, Kong X, Ding M. Fault Diagnosis of Natural Ester Oil Filled Transformers Using Mechanism Inspired Structured Tokens and Auxiliary Supervision with Full Window Trends. Inventions. 2026;11(6):131. doi:10.3390/inventions11060131

BibTeX
@article{Zhang2026,
  author = {Zhang, Chengfei and Sun, Mingze and Cao, Zhan and Kong, Xiangzhuo and Ding, Man},
  title = {Fault Diagnosis of Natural Ester Oil Filled Transformers Using Mechanism Inspired Structured Tokens and Auxiliary Supervision with Full Window Trends},
  journal = {Inventions},
  year = {2026},
  volume = {11},
  number = {6},
  pages = {131},
  doi = {10.3390/inventions11060131}
}