EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Numerical Simulation of Gas Leakage from an Integrated CNG–Hydrogen Energy Supply Station for Vehicles

Taibi He, Lin Wang, Kunpeng Gao, Tianqing Cao, Yidong Wang

Fire · 19.11.2026 · 9 (11) · 524

DOI: 10.3390/fire9110524 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Fire, online erschienen am 19.11.2026. Verfasst von Taibi He und 4 weiteren Autor:innen. Die Arbeit nennt 59 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Major Science and Technology Special Project of Sichuan Province.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Integrated CNG–hydrogen refueling stations place two pressurized fuels in a shared, obstructed geometry, but controlled evidence on their coupled dispersion is limited. A three-dimensional transient CFD model of a representative, non-site-specific station layout developed in accordance with GB 50156-2021 was used for 17 continuous-release scenarios (6 s) spanning leakage mode, location, categorical direction, aperture (8–15 mm), and crosswind (0–10 m/s). The source model used ideal-gas choked-flow relations at 45 MPa (H2) and 20 MPa (CH4) with Cd = 1.0; this is a bounding source-strength assumption, not a calibrated orifice coefficient. Model assessment was limited to grid/time-step sensitivity and quantitative axial comparison with a small-scale hydrogen-free jet. In windless open-process-area Cases 5–9 and 14–17, the H2/CH4 volume ratio was 6.16–6.85, and normalized in-domain volumes were 62.3–66.6 and 7.67–8.59 m3 per (kg/s), respectively. Simultaneous dispenser releases reduced the hydrogen volume from 90.31 to 70.13 m3 (22.3%) but increased methane from 20.41 to 21.94 m3 (7.5%), demonstrating non-superposition. Wind cases fell outside the windless ranges; at 10 m/s the ratio was 5.72 and the normalized hydrogen volume was 45.1 m3 per (kg/s). These changes combine mixing, advection, obstacle interaction, and boundary outflow. Case 4 reached the 30 m domain ceiling, so its volume is an in-domain residual rather than a total cloud volume. Case 16 gave the largest simulated in-domain volumes (325.87 m3 H2; 50.37 m3 CH4). The results quantify dispersion only and do not establish accident probability, ignition consequences, or off-site extents.

Förderung

  • Major Science and Technology Special Project of Sichuan Province

Zitieren

APA

He, T., Wang, L., Gao, K., Cao, T., & Wang, Y. (2026). Numerical Simulation of Gas Leakage from an Integrated CNG–Hydrogen Energy Supply Station for Vehicles. Fire, 9(11), 524. https://doi.org/10.3390/fire9110524

Vancouver

He T, Wang L, Gao K, Cao T, Wang Y. Numerical Simulation of Gas Leakage from an Integrated CNG–Hydrogen Energy Supply Station for Vehicles. Fire. 2026;9(11):524. doi:10.3390/fire9110524

BibTeX
@article{He2026,
  author = {He, Taibi and Wang, Lin and Gao, Kunpeng and Cao, Tianqing and Wang, Yidong},
  title = {Numerical Simulation of Gas Leakage from an Integrated CNG–Hydrogen Energy Supply Station for Vehicles},
  journal = {Fire},
  year = {2026},
  volume = {9},
  number = {11},
  pages = {524},
  doi = {10.3390/fire9110524}
}
Kostenlos starten →