Experimental Study on Immersion Cooling Technology for LIBs Using HFE-7200 Coolant
Fire · 07.11.2026 · 9 (11) · 496
DOI: 10.3390/fire9110496 ↗Kurz gefasst
Fachartikel in der Zeitschrift Fire, online erschienen am 07.11.2026. Verfasst von Haiting Wu und 4 weiteren Autor:innen. Die Arbeit nennt 50 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: The Key Laboratory of Fire Protection Technology for Industry and Public Building, Ministry of Emergency Management, Tianjin Key Laboratory of Fire Safety Technology, Key Science and Technology Program of the MEM.
Abstract (Originalsprache)
Immersion liquid cooling is a thermal runaway protection strategy for lithium-ion batteries; however, the regulatory mechanism of immersion depth on battery thermal runaway remains unclear. In this study, 18650-type ternary lithium-ion batteries with capacities of 2000, 2600, and 3200 mAh were selected as research objects, and HFE-7200 dielectric fluorinated liquid was used as the cooling medium. A self-built immersion battery thermal runaway test platform was employed to investigate the influence of immersion depth on thermal runaway characteristic parameters. The kinetic laws of temperature variation, thermal runaway mass loss, and toxic gases, including CO, NO2, NH3, and HF, were discussed. The results show that immersion depth exerts a nonlinear regulatory effect on thermal runaway. Shallow immersion of 1–2 cm cools the lower part of the cell, prolongs the thermal runaway incubation time, and may intensify thermal runaway, whereas deep immersion of 3–4 cm can effectively suppress thermal runaway. When thermal runaway was effectively suppressed, the maximum system temperature was 264.3 °C. The average mass loss rates of the 2000, 2600, and 3200 mAh batteries under different immersion depths were 16.2%, 18.6%, and 38.8%, respectively. The release sequence of the four major toxic gases during battery thermal runaway was determined, and their peak concentrations were compared. A three-zone heat transfer model was established along the battery axial direction, clarifying that the proportional changes of the fully cooled zone, vapor-liquid coupling transition zone, and unimmersed runaway zone jointly govern the heat generation and heat transfer balance of the cell. This study can provide a quantitative experimental basis and theoretical support for safety liquid level calibration of immersion liquid cooling battery systems.
Förderung
- The Key Laboratory of Fire Protection Technology for Industry and Public Building, Ministry of Emergency Management
- Tianjin Key Laboratory of Fire Safety Technology
- Key Science and Technology Program of the MEM
- Fundamental Research Funds for the Central Universities
Zitieren
APA
Wu, H., Ge, M., Li, M., Kang, X., & Yin, Z. (2026). Experimental Study on Immersion Cooling Technology for LIBs Using HFE-7200 Coolant. Fire, 9(11), 496. https://doi.org/10.3390/fire9110496
Vancouver
Wu H, Ge M, Li M, Kang X, Yin Z. Experimental Study on Immersion Cooling Technology for LIBs Using HFE-7200 Coolant. Fire. 2026;9(11):496. doi:10.3390/fire9110496
BibTeX
@article{Wu2026,
author = {Wu, Haiting and Ge, Muying and Li, Mengting and Kang, Xingjian and Yin, Zhipeng},
title = {Experimental Study on Immersion Cooling Technology for LIBs Using HFE-7200 Coolant},
journal = {Fire},
year = {2026},
volume = {9},
number = {11},
pages = {496},
doi = {10.3390/fire9110496}
}
EUVIMED