Numerical Investigation on Thermal-Mechanical Coupling Behavior and Fire Resistance Performance of Steel Structures in Substation Fires
Fire · 27.04.2026 · 9 (5) · 183
DOI: 10.3390/fire9050183 ↗Kurz gefasst
Fachartikel in der Zeitschrift Fire, online erschienen am 27.04.2026. Verfasst von Lvchao Qiu und 8 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Science and Technology Project of State Grid Zhejiang Electric Power Co., Ltd..
Abstract (Originalsprache)
Transformer fires within indoor substations constitute severe hydrocarbon fire scenarios characterized by rapid heat release rates and extreme peak temperatures, posing a critical threat to the structural integrity of steel frameworks and power grid stability. To rigorously assess structural safety under such conditions, this study employs a sequential thermal-mechanical coupled numerical methodology combining Computational Fluid Dynamics (CFD) and Finite Element Analysis (FEA). Focusing on a 110 kV indoor substation, the research simulates the transient, non-uniform temperature fields induced by transformer oil combustion and analyzes the thermo-mechanical response of key steel components. Furthermore, the protective efficacy of two non-intumescent coatings (Material A and Material B) with distinct thermal conductivities is systematically evaluated. Computational results elucidate significant thermal stratification, with upper-level structures sustaining exposure to temperatures exceeding 1500 K. Unprotected steel components subjected to direct flame impingement exhibit severe stress concentrations and plastic deformation, reaching their load-bearing limit within 4825 s. The application of fire-retardant coatings markedly enhances fire resistance; a 5 mm layer of Material A (λ = 0.20 W/(m·K)) extends the time to failure to approximately 9390 s. Notably, increasing the thickness of Material A to 20 mm, or alternatively employing a 10 mm layer of Material B (λ = 0.10 W/(m·K)), effectively mitigates thermal stress concentrations. This ensures structural deformation remains within safe limits throughout a 3 h (10,800 s) fire duration. This study provides a theoretical basis and quantitative engineering references for the optimal fire protection design of substation steel structures.
Förderung
- Science and Technology Project of State Grid Zhejiang Electric Power Co., Ltd.
Zitieren
APA
Qiu, L., Zhou, Z., Ou, W., Zhou, Y., Hu, J., Zhao, Z., Liu, H., Lu, K., & Jian, S. (2026). Numerical Investigation on Thermal-Mechanical Coupling Behavior and Fire Resistance Performance of Steel Structures in Substation Fires. Fire, 9(5), 183. https://doi.org/10.3390/fire9050183
Vancouver
Qiu L, Zhou Z, Ou W, Zhou Y, Hu J, Zhao Z, et al. Numerical Investigation on Thermal-Mechanical Coupling Behavior and Fire Resistance Performance of Steel Structures in Substation Fires. Fire. 2026;9(5):183. doi:10.3390/fire9050183
BibTeX
@article{Qiu2026,
author = {Qiu, Lvchao and Zhou, Zheng and Ou, Wenjun and Zhou, Yutong and Hu, Jingrui and Zhao, Zhoufeng and Liu, Huimin and Lu, Kuangda and Jian, Shouwei},
title = {Numerical Investigation on Thermal-Mechanical Coupling Behavior and Fire Resistance Performance of Steel Structures in Substation Fires},
journal = {Fire},
year = {2026},
volume = {9},
number = {5},
pages = {183},
doi = {10.3390/fire9050183}
}
EUVIMED