Precise Algorithm of Ultra-Early Fire Detection and Localization for Active Sprinkler Systems in High-Rack Warehouses
Fire · 06.03.2026 · 9 (3) · 118
DOI: 10.3390/fire9030118 ↗Kurz gefasst
Fachartikel in der Zeitschrift Fire, online erschienen am 06.03.2026. Verfasst von Jiajie Qin und 4 weiteren Autor:innen. Die Arbeit nennt 35 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Ministry of Science and Technology of the People's Republic of China, Tianjin Science and Technology Bureau, Tianjin Fire Science and Technology Research Institute of MEM.
Abstract (Originalsprache)
The prevalence of high-rack warehouses and large-space facilities with high ceilings poses significant challenges to traditional automatic sprinkler systems, which often exhibit activation delays and limited suppression efficacy. This study investigates the spatio-temporal evolution and distribution characteristics of fire-induced thermal smoke flow through a hybrid approach combining full-scale fire experiments and numerical simulations. A physical hypothesis is proposed: the ceiling temperature field approximately follows a two-dimensional Gaussian distribution. Through parametric numerical simulations under varied ambient temperatures, fire identification criteria were calibrated, encompassing a sustained increase in the average temperature rise within high-temperature zones, the attainment of a predefined threshold, and the spatial stabilization of the Gaussian distribution center. Subsequently, a precise algorithm for rapid fire identification and source localization was developed. Experimental validation demonstrates that the proposed algorithm significantly outperforms traditional passive-activation closed sprinklers, advancing fire detection by 46–67 s. Furthermore, the fire source localization error is maintained within half of the sprinkler spacing. The algorithm also exhibits robust environmental adaptability and generalizability across a wide ambient temperature range, providing a technical foundation for active-actuation fire suppression.
Förderung
- Ministry of Science and Technology of the People's Republic of China
- Tianjin Science and Technology Bureau
- Tianjin Fire Science and Technology Research Institute of MEM
- The Multiple Investment in Applied Basic Research of Tianjin
Zitieren
APA
Qin, J., Huang, Z., Liu, X., Li, J., & Zhang, W. (2026). Precise Algorithm of Ultra-Early Fire Detection and Localization for Active Sprinkler Systems in High-Rack Warehouses. Fire, 9(3), 118. https://doi.org/10.3390/fire9030118
Vancouver
Qin J, Huang Z, Liu X, Li J, Zhang W. Precise Algorithm of Ultra-Early Fire Detection and Localization for Active Sprinkler Systems in High-Rack Warehouses. Fire. 2026;9(3):118. doi:10.3390/fire9030118
BibTeX
@article{Qin2026,
author = {Qin, Jiajie and Huang, Zhangfeng and Liu, Xin and Li, Jingjing and Zhang, Wenbin},
title = {Precise Algorithm of Ultra-Early Fire Detection and Localization for Active Sprinkler Systems in High-Rack Warehouses},
journal = {Fire},
year = {2026},
volume = {9},
number = {3},
pages = {118},
doi = {10.3390/fire9030118}
}
EUVIMED