EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Pyrolysis Kinetics and Gas Evolution of Flame-Retardant PVC and PE: A TG-FTIR-GC/MS Study

Wen-Wei Su, Yang Li, Peng-Rui Man, Ya-Wen Sheng, Jian Wang

Fire · 30.06.2025 · 8 (7) · 262

DOI: 10.3390/fire8070262 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Fire, online erschienen am 30.06.2025. Verfasst von Wen-Wei Su und 4 weiteren Autor:innen. Die Arbeit wurde bisher 14-mal zitiert (Crossref) und nennt 44 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: The National Key Research and Development Program of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The insulation layer of flame-retardant cables plays a critical role in mitigating fire hazards by influencing toxic gas emissions and the accuracy of fire modeling. This study systematically explores the pyrolysis kinetics and volatile gas evolution of flame-retardant polyvinyl chloride (PVC) and polyethylene (PE) insulation materials using advanced TG-FTIR-GC/MS techniques. Distinct pyrolysis stages were identified through thermogravimetric analysis (TGA) at heating rates of 10–40 K/min, while the KAS model-free method and Málek fitting function quantified activation energies and reaction mechanisms. Results revealed that flame-retardant PVC undergoes two major stages: (1) dehydrochlorination, characterized by the rapid release of HCl and low activation energy, and (2) main-chain scission, producing aromatic compounds that contribute to fire toxicity. In contrast, flame-retardant PE demonstrates a more stable pyrolysis process dominated by random chain scission and the formation of a dense char layer, significantly enhancing its flame-retardant performance. FTIR and GC/MS analyses further highlighted distinct gas evolution behaviors: PVC primarily generates HCl and aromatic hydrocarbons, whereas PE releases olefins and alkanes with significantly lower toxicity. Additionally, the application of a classification and regression tree (CART) model accurately predicted mass loss behavior under various heating rates, achieving exceptional fitting accuracy (R2 > 0.98). This study provides critical insights into the pyrolysis mechanisms of flame-retardant cable insulation and offers a robust data framework for optimizing fire modeling and improving material design.

Förderung

  • The National Key Research and Development Program of China

Zitieren

APA

Su, W., Li, Y., Man, P., Sheng, Y., & Wang, J. (2025). Pyrolysis Kinetics and Gas Evolution of Flame-Retardant PVC and PE: A TG-FTIR-GC/MS Study. Fire, 8(7), 262. https://doi.org/10.3390/fire8070262

Vancouver

Su W, Li Y, Man P, Sheng Y, Wang J. Pyrolysis Kinetics and Gas Evolution of Flame-Retardant PVC and PE: A TG-FTIR-GC/MS Study. Fire. 2025;8(7):262. doi:10.3390/fire8070262

BibTeX
@article{Su2025,
  author = {Su, Wen-Wei and Li, Yang and Man, Peng-Rui and Sheng, Ya-Wen and Wang, Jian},
  title = {Pyrolysis Kinetics and Gas Evolution of Flame-Retardant PVC and PE: A TG-FTIR-GC/MS Study},
  journal = {Fire},
  year = {2025},
  volume = {8},
  number = {7},
  pages = {262},
  doi = {10.3390/fire8070262}
}
Kostenlos starten →