Freeze Thickness Prediction of Fire Pipes in Low-Temperature Environment Based on CFD and Artificial Neural Network
Fire · 05.02.2025 · 8 (2) · 65
DOI: 10.3390/fire8020065 ↗Kurz gefasst
Fachartikel in der Zeitschrift Fire, online erschienen am 05.02.2025. Verfasst von Yubiao Huang und 4 weiteren Autor:innen. Die Arbeit wurde bisher 3-mal zitiert (Crossref) und nennt 39 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: the Science and Technology Project of State Grid Corporation of China.
Abstract (Originalsprache)
In cold regions, fire pipes are highly susceptible to freezing, which can obstruct water flow and lead to pipe ruptures. Accurately predicting the freeze thickness is crucial to maintaining the functionality of fire protection systems. Traditional methods for predicting fire pipe freezing often rely on simplified models or time-consuming simulations, which limits their accuracy in complex environments. A model for predicting the freeze thickness of fire pipes under low-temperature conditions was developed by integrating Computational Fluid Dynamics with an Artificial Neural Network (ANN). The CFD model was validated to generate data for training and optimizing an ANN based on collected experimental data. The CFD results demonstrate a nonlinear relationship between the freeze thickness of the fire pipe, ambient temperature, and time. Afterwards, the optimal ANN topology, determined through hyperparameter tuning, was found to consist of 12 neurons, the trainlm training function, and tansig–purelin activation functions. Eventually, the ANN model achieved high prediction accuracy with a mean squared error (MSE) of 6.62 × 10−4 on the test set and a regression coefficient R greater than 0.98 across all datasets. Furthermore, the ANN model agrees closely with the simulated data, not only for trained temperature conditions (−5 °C to −50 °C) but also for unseen temperature conditions (−55 °C and −60 °C), indicating excellent generalization performance.
Förderung
- the Science and Technology Project of State Grid Corporation of China
Zitieren
APA
Huang, Y., Zhang, J., Zhong, Y., Guo, Y., & Ding, Y. (2025). Freeze Thickness Prediction of Fire Pipes in Low-Temperature Environment Based on CFD and Artificial Neural Network. Fire, 8(2), 65. https://doi.org/10.3390/fire8020065
Vancouver
Huang Y, Zhang J, Zhong Y, Guo Y, Ding Y. Freeze Thickness Prediction of Fire Pipes in Low-Temperature Environment Based on CFD and Artificial Neural Network. Fire. 2025;8(2):65. doi:10.3390/fire8020065
BibTeX
@article{Huang2025,
author = {Huang, Yubiao and Zhang, Jiaqing and Zhong, Yu and Guo, Yi and Ding, Yanming},
title = {Freeze Thickness Prediction of Fire Pipes in Low-Temperature Environment Based on CFD and Artificial Neural Network},
journal = {Fire},
year = {2025},
volume = {8},
number = {2},
pages = {65},
doi = {10.3390/fire8020065}
}